ICAF - 

Integrated Compressed Air Foam System

 

Air Supply Section 

 

 

FM-0723-0-12 B

 

3. Operation 

 

.1  To OPEN Air Supply: 

.a  Before opening any cylinder valve, verify that the 

piping between the cylinder bank and the ICAF 
System is properly installed and secured. 

.b  Slowly open one cylinder valve 

(C4)

 and check for 

any leak between the cylinder valve, the manifold 
and the ICAF System air supply line 

(circled item 4)

If there is no leak, pressure will build up in the 
manifold and the piping. 

.c  Once pressure is stabilized, pressure gauge 

(C6)

 

should indicate a minimum pressure of 2200 psi. and 
pressure transducer 

(C7)

 should indicate a normal 

status at the ARC-1 Release controller. 

.d Air 

pressure 

gauge 

(A4) 

inside the ICAF System 

cabinet should indicate a pressure of 100 psi.  Refer 
to TRIM SCHEMATIC section. 

.e  Open all of the remaining cylinders. 

.2  To CLOSE air supply:  

.a  Close all cylinders valves 

(C4).

  

.b  Bleed system manifold and air supply line by opening 

system flushing valve 

(A3).

 Refer to TRIM 

SCHEMATIC section. 

4. Recharge 

cylinders: 

After a system discharge or when cylinder pressure is under 
the minimum recommended pressure, cylinders must be 
refilled with dry air to a storage pressure of 2400 psi @ 70

°

(16,536 kPa @ 21

°

C). The following steps must be followed 

before sending the cylinders for refilling. 

.a  Close all cylinder valves 

(C4).

 

.b  Bleed system manifold and air supply line by opening 

system flushing valve 

(A3).

 Refer to TRIM 

SCHEMATIC section. 

.c  After all the pressure is removed, pressure gauge 

(C6)

 should indicate a pressure of 0 psi. 

.d Remove pressure regulator assembly 

(C5)

 and 

pressure gauge 

(C6).

 

.e  Properly plug manifold outlet to prevent any dirt from 

contaminating manifold during transport.  

NOTICE:  

Empty cylinders must be recharged by FireFlex 

or its trained authorized agent.  Contact FireFlex After 
Sales Support Department for information about the 
nearest authorized agent to your location. 

5.  Maintenance and inspection: 

Regular inspections, tests, and maintenance should be 
performed at intervals specified in this document to verify that 
the air supply is in good operating condition and that it 
functions as intended.  

Cylinder inspection: 

Storage air pressure shall be checked at least semi-annually.  
If the air cylinders bank shows a pressure under 2200 psi. it 
shall be refilled or replaced. 

Hydrostatic test: 

High-pressure cylinders used in ICAF systems shall not be 
recharged without a hydrostatic test (and remarking) if more 
than 5 years have elapsed from the date of the last test. 
Cylinders continuously in service without discharging shall be 
permitted to be retained in service for a maximum of 12 years 
from the date of the last hydrostatic test. At the end of 12 
years, they shall be discharged and retested before being 
returned to service. 

Cylinders continuously in service without discharging shall be 
given a complete external visual inspection every 5 years or 
more frequently if required. The visual inspection shall be in 
accordance with Section 3 of CGA C-6, Standard for Visual 
Inspection of Steel Compressed Gas Cylinders, except that 
the cylinders need not be emptied or stamped while under 
pressure. Inspections shall be made only by competent 
personnel and the results recorded on both of the following: 

(1)   A record tag permanently attached to each cylinder 

(2)   A suitable inspection report 

A completed copy of the inspection report shall be furnished 
to the owner of the system or an authorized representative. 
These records shall be retained by the owner for the life of 
the system. 

Where external visual inspection indicates that the container 
has been damaged, additional strength tests shall be 
required. 

 

Содержание ARC-1

Страница 1: ...Operation Maintenance Manual FM 0723 0 02 A...

Страница 2: ...Integrated Compressed Air Foam System with Electric Release Owner s Operation and Maintenance Manual FM 0723 0 04 A...

Страница 3: ...Integrated Compressed Air Foam System FM 0723 0 04 A FireFlex Systems Inc 1935 Lionel Bertrand Blvd Boisbriand QC Canada J7H 1N8 Tel 450 437 3473 Toll free 866 347 3353 Fax 450 437 1930 Web Site http...

Страница 4: ...n Preliminary inspection before placing the system in service Placing the system in service Important settings Mechanical trim section 1 System operation Post discharge instructions Inspection tests a...

Страница 5: ...ystem 3 Operation 4 Recharge cylinders 5 Maintenance and Inspection Foam Supply Section FM 0723 0 13 1 Foam storage tank 2 Foam concentrate 3 Foam tank design and selection 4 Interconnection piping to...

Страница 6: ...l is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FireFlex Systems Inc assumes no liability resulting from any errors or omissions i...

Страница 7: ...OWNER S OPERATION MAINTENANCE MANUAL ICAF Integrated Compressed Air Foam System FM 0723 0 04 A...

Страница 8: ...g air under pressure water and foam concentrate in the right proportions and then sending it through piping for distribution on the protected area Integrated Compressed Air Foam ICAF Systems for fixed...

Страница 9: ...guration required to supply the nozzles in the hazard s Remote Controlled Unit This unit is used when an additional zone is required to be protected by the same system This unit includes all the mecha...

Страница 10: ...1 Control Panel energizes the Solenoid Valve R2 open the pneumatic control line is then pressurized causing the water air and foam pneumatically activated control valves A1 B9 F1 to open simultaneous...

Страница 11: ...upply must be CLOSED see AIR SUPPLY SECTION Flow Test Valve B6 and main drain valve B16 must be CLOSED Alarm test valve B5 must be CLOSED Emergency Release valve R1 is CLOSED System flushing valve A3...

Страница 12: ...line vent Solenoid Valve is closed R4 Electric Release In the SET condition water supply pressure is trapped in the priming chamber by a spring loaded check valve B4 and the normally closed water pneu...

Страница 13: ...Prior to proceeding notify all Authorities Having Jurisdiction Consideration should be given to employ a fire patrol in the affected areas ICAF Systems that have been exposed to a fire must be returne...

Страница 14: ...en full flow develops from Flow Test Valve B6 close the Flow Test Valve Verify that there is no flow from the System Main Drain Valves B16 11 Close the System Main Drain Valve s B16 12 Fully open and...

Страница 15: ...those established in this document 3 These tasks shall be performed by FireFlex s authorized personnel who have developed competence through training and experience 4 It is the responsibility of the...

Страница 16: ...dicates that normal pressure is being maintained The flow control valve shall be externally inspected to verify the following 1 The valve is free from physical damage 2 All trim valves are in the appr...

Страница 17: ...lapse between operation of detection systems and water delivery time to the protected area shall be recorded for open discharge devices Discharge Patterns The discharge patterns from all of the nozzl...

Страница 18: ...ng upon subsequent alarm GROUND FAULT A yellow lamp that illuminates steadily during a ground fault condition PARTIAL DISABLE A yellow lamp that illuminates steadily when any input or output circuit i...

Страница 19: ...duly acknowledged a full reset sequence should take only a few seconds to complete Under normal conditions pressing on the SYSTEM RESET key make the local sounder beep once and will also perform a LAM...

Страница 20: ...additional details In the TIMER STATUS screen all the set values of the various timers are displayed as shown in the example below actual screen may differ depending on system configuration Pressing o...

Страница 21: ...below Note Should the start up routine take more than 2 minutes and system seems to be hung perform a cold reset by removing power to the unit and back If problem continues contact your nearest FireF...

Страница 22: ...lays a 5 digit code used by the factory describing module placement circuit type zone number and type of activation Refer to TROUBLESHOOTING in Appendix D for additional details on these codes DATE di...

Страница 23: ...off function is provided The CAF discharge can be manually suspended using the following sequence of operation 1 Press and hold the function key F3 labelled System Shut Off on the keypad of the ARC 1...

Страница 24: ...ement Detail 12 12 BCA Grounding Bar 12 TBB N U Factory Wired TBB Module 1 2 3 4 6 5 Releasing Panel Control Modules 8 3 7 2 Input Output Modules Blank 1 9 N U 8 7 11 10 Blank Blank 1 2 3 4 PSA Transd...

Страница 25: ...rface FACTORY WIRING SOA Module Supervised Output Circuits TYPICAL CLASS B STYLE Z CIRCUITS FACTORY WIRING ARA Module Auxiliary Relay Outputs SIA Module Supervised Input Zones TYPICAL CLASS B STYLE B...

Страница 26: ...ushing valve F5 must both be CLOSED All gauges B11 B12 and E3 should show 0 psi pressure Foam concentrate tank T1 must be filled according to the procedure described in the FOAM SUPPLY section Compres...

Страница 27: ...Page 2 of 4 ICAF Integrated Compressed Air Foam System System Trim Section FM 0723 0 09 A Trim Schematic System with electric release...

Страница 28: ...heck valve B9 Water pneumatically actuated control valve N C B10 Water supply control valve B11 Priming pressure water gauge valve B12 Water supply presure gauge valve B13 Clapper check valve B14 Flow...

Страница 29: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System System Trim Section FM 0723 0 09 A...

Страница 30: ...o protective caps have to be removed and most importantly no tubing or fittings are required to be installed after receiving The cylinders bank is also provided with a refilling outlet C9 which allows...

Страница 31: ...rs must be recharged by FireFlex or its trained authorized agent Contact FireFlex After Sales Support Department for information about the nearest authorized agent to your location 5 Maintenance and i...

Страница 32: ...23 0 12 B Figure 2 Compressed Air Cylinders Bank Rack mounted Air supply Components C1 Cylinders rack C2 Compressed air cylinder C3 Safety release disk C4 Cylinder valve C5 Pressure regulator C6 Press...

Страница 33: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System Air Supply Section FM 0723 0 12 B This page is left blank intentionally...

Страница 34: ...For further details see the Foam Concentrate Data Sheet Environmental and Toxicological Information Foam concentrates used with Compressed Air Foam Systems are biodegradable However as with any subst...

Страница 35: ...tube is drained CLOSE tank drain valve T3 both sight gauge isolation valves T4 and the tank refill vent valve T6 b If level is below normal add foam concentrate up to normal level by following FILLIN...

Страница 36: ...en from the Storage tank drain valve T3 Foam samples may be sent to FireFlex Systems Either glass or plastic bottles are satisfactory provided they are leak proof and well packaged The sample s must b...

Страница 37: ...approximately 1 minute or until pressure stabilizes at the Foam injection line pressure gauge F4 4 CLOSE foam injector flushing valve F5 5 Foam injection line pressure gauge F4 should vent quickly and...

Страница 38: ...13 D Figure 2 Foam storage tank schematic Foam storage tank components T1 Foam storage tank T2 Dip tube T3 Storage tank drain valve T4 Level sight gauge isolation valve T5 Foam level sight gauge T6 Fo...

Страница 39: ...Page 6 of 6 ICAF Integrated Compressed Air Foam System Foam Supply Section FM 0723 0 13 D This page is left blank intentionally...

Страница 40: ...on system auxiliary contacts and signaling devices Knockouts can be drilled by the installing contractor on site but have to meet the restrictions indicated on Figure 2 Gauges to indicate air water su...

Страница 41: ...te to access anchoring holes 2 MAX W SIZE VARIES ACCORDING TO MIXING CHAMBER SIZE SCH 40 GROOVED OUTLET MIXING CHAMBER 1 MIXING CHAMBER 2 SCH 40 GROOVED OUTLET OPTIONAL OUTLET DRILLED ONLY WHEN 2 nd M...

Страница 42: ...only to avoid internal components and about 1 2 from cabinet rear edge as shown 5 3 9 15 FM 072C 0 251 B dwg Wiring Routing Wiring shown in Figure 3 below indicates typical Wiring Routing for Power Li...

Страница 43: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System System Characteristics Section FM 0723 0 14 C This page is left blank intentionally...

Страница 44: ...Page 1 of 2 ICAF Integrated Compressed Air Foam System Notes Warranty FM 0723 0 16 B User Notes...

Страница 45: ...ow long an expressed warranty lasts so the above limitations may not apply to you Under no circumstances shall the Manufacturer be liable for any loss of or damage to property direct or indirect incid...

Отзывы: