Page 10 of 10

 

 

ICAF

 - Integrated Compressed Air Foam System 

Inspection & Maintenance Section 

 

FM-0723-0-07 C

 

Annually: 

TEST: 

Control Valve: 

Each control valve shall be operated through its full range 
and returned to its normal position. 

Main Drain: 

A main drain test shall be conducted to determine whether 
there has been a change in the condition of the water supply 
piping and control valves. 

Operational Test: 

Operational tests shall be conducted to ensure that the ICAF 
System responds as designed, both automatically and 
manually. 

The test procedures shall simulate anticipated emergency 
events so the response of the ICAF System can be 
evaluated. 

Protection shall be provided for any devices or equipment 
subject to damage by system discharge during tests. 

Where the nature of the protected property is such that CAF 
cannot be discharged for test purposes, the trip test shall be 
conducted in a manner that does not necessitate discharge 
in the protected area. 

Where the nature of the protected property is such that CAF 
cannot be discharged unless protected equipment is shut 
down (e.g., energized electrical equipment), a full flow 
system test shall be conducted at the next scheduled 
shutdown. In all cases, the test frequency shall not exceed 3 
years. 

Where discharge from the system discharge devices would 
create a hazardous condition or conflict with local 
requirements, an approved alternate method to achieve full 
flow conditions shall be permitted. 

Response Time: 

Under test conditions, the automatic fire detection systems, 
when exposed to a test source, shall operate within the 
requirements of NFPA 72, National Fire Alarm Code, for the 
type of detector provided and the response time shall be 
recorded. 

Discharge Time: 

The time lapse between operation of detection systems and 
water delivery time to the protected area shall be recorded 
for open discharge devices. 

Discharge Patterns: 

The discharge patterns from all of the nozzles shall be 
observed to ensure that patterns are not impeded by plugged 
nozzles and to ensure that nozzles are correctly positioned 
and that obstructions do not prevent discharge patterns from 
covering surfaces to be protected. 

Where obstructions occur, the piping and nozzles shall be 
cleaned and the system retested. 

 

Pressure Readings: 

Pressure readings shall be recorded at the main control valve 
and the CAF outlet. 

Readings shall be compared to the design pressures to 
ensure the original system design requirements are met. 

Multiple Systems: 

The maximum number of systems expected to operate in 
case of fire shall be tested simultaneously to check the 
adequacy of the water supply. 

Manual Operation: 

Manual actuation devices shall be tested. 

Return to Service:  

After the full flow test, the system shall be returned to service 
in accordance with the instructions described in this manual. 

Low points in the ICAF System shall be drained after each 
operation. 

Records indicating the date the ICAF System was last tripped 
and the tripping time as well as the individual and 
organization conducting the test shall be maintained at a 
location or in a manner readily available for review by the 
Authority Having Jurisdiction. 

MAINTENANCE: 

Strainers: 

Priming line strainer (basket or screen) shall be removed, 
cleaned and inspected. 

Every 5 years: 

TEST: 

Gauges:  

Gauges shall be tested every 5 years by comparison with a 
calibrated gauge. Gauges not accurate to within 3 percent of 
the full scale shall be recalibrated or replaced. 

INSPECTION: 

Flow Control Valve: 

The interior of the flow control valve shall be inspected to 
verify that all components operate properly. Internal 
components shall be cleaned, repaired, or replaced as 
necessary. 

Содержание ARC-1

Страница 1: ...Operation Maintenance Manual FM 0723 0 02 A...

Страница 2: ...Integrated Compressed Air Foam System with Electric Release Owner s Operation and Maintenance Manual FM 0723 0 04 A...

Страница 3: ...Integrated Compressed Air Foam System FM 0723 0 04 A FireFlex Systems Inc 1935 Lionel Bertrand Blvd Boisbriand QC Canada J7H 1N8 Tel 450 437 3473 Toll free 866 347 3353 Fax 450 437 1930 Web Site http...

Страница 4: ...n Preliminary inspection before placing the system in service Placing the system in service Important settings Mechanical trim section 1 System operation Post discharge instructions Inspection tests a...

Страница 5: ...ystem 3 Operation 4 Recharge cylinders 5 Maintenance and Inspection Foam Supply Section FM 0723 0 13 1 Foam storage tank 2 Foam concentrate 3 Foam tank design and selection 4 Interconnection piping to...

Страница 6: ...l is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FireFlex Systems Inc assumes no liability resulting from any errors or omissions i...

Страница 7: ...OWNER S OPERATION MAINTENANCE MANUAL ICAF Integrated Compressed Air Foam System FM 0723 0 04 A...

Страница 8: ...g air under pressure water and foam concentrate in the right proportions and then sending it through piping for distribution on the protected area Integrated Compressed Air Foam ICAF Systems for fixed...

Страница 9: ...guration required to supply the nozzles in the hazard s Remote Controlled Unit This unit is used when an additional zone is required to be protected by the same system This unit includes all the mecha...

Страница 10: ...1 Control Panel energizes the Solenoid Valve R2 open the pneumatic control line is then pressurized causing the water air and foam pneumatically activated control valves A1 B9 F1 to open simultaneous...

Страница 11: ...upply must be CLOSED see AIR SUPPLY SECTION Flow Test Valve B6 and main drain valve B16 must be CLOSED Alarm test valve B5 must be CLOSED Emergency Release valve R1 is CLOSED System flushing valve A3...

Страница 12: ...line vent Solenoid Valve is closed R4 Electric Release In the SET condition water supply pressure is trapped in the priming chamber by a spring loaded check valve B4 and the normally closed water pneu...

Страница 13: ...Prior to proceeding notify all Authorities Having Jurisdiction Consideration should be given to employ a fire patrol in the affected areas ICAF Systems that have been exposed to a fire must be returne...

Страница 14: ...en full flow develops from Flow Test Valve B6 close the Flow Test Valve Verify that there is no flow from the System Main Drain Valves B16 11 Close the System Main Drain Valve s B16 12 Fully open and...

Страница 15: ...those established in this document 3 These tasks shall be performed by FireFlex s authorized personnel who have developed competence through training and experience 4 It is the responsibility of the...

Страница 16: ...dicates that normal pressure is being maintained The flow control valve shall be externally inspected to verify the following 1 The valve is free from physical damage 2 All trim valves are in the appr...

Страница 17: ...lapse between operation of detection systems and water delivery time to the protected area shall be recorded for open discharge devices Discharge Patterns The discharge patterns from all of the nozzl...

Страница 18: ...ng upon subsequent alarm GROUND FAULT A yellow lamp that illuminates steadily during a ground fault condition PARTIAL DISABLE A yellow lamp that illuminates steadily when any input or output circuit i...

Страница 19: ...duly acknowledged a full reset sequence should take only a few seconds to complete Under normal conditions pressing on the SYSTEM RESET key make the local sounder beep once and will also perform a LAM...

Страница 20: ...additional details In the TIMER STATUS screen all the set values of the various timers are displayed as shown in the example below actual screen may differ depending on system configuration Pressing o...

Страница 21: ...below Note Should the start up routine take more than 2 minutes and system seems to be hung perform a cold reset by removing power to the unit and back If problem continues contact your nearest FireF...

Страница 22: ...lays a 5 digit code used by the factory describing module placement circuit type zone number and type of activation Refer to TROUBLESHOOTING in Appendix D for additional details on these codes DATE di...

Страница 23: ...off function is provided The CAF discharge can be manually suspended using the following sequence of operation 1 Press and hold the function key F3 labelled System Shut Off on the keypad of the ARC 1...

Страница 24: ...ement Detail 12 12 BCA Grounding Bar 12 TBB N U Factory Wired TBB Module 1 2 3 4 6 5 Releasing Panel Control Modules 8 3 7 2 Input Output Modules Blank 1 9 N U 8 7 11 10 Blank Blank 1 2 3 4 PSA Transd...

Страница 25: ...rface FACTORY WIRING SOA Module Supervised Output Circuits TYPICAL CLASS B STYLE Z CIRCUITS FACTORY WIRING ARA Module Auxiliary Relay Outputs SIA Module Supervised Input Zones TYPICAL CLASS B STYLE B...

Страница 26: ...ushing valve F5 must both be CLOSED All gauges B11 B12 and E3 should show 0 psi pressure Foam concentrate tank T1 must be filled according to the procedure described in the FOAM SUPPLY section Compres...

Страница 27: ...Page 2 of 4 ICAF Integrated Compressed Air Foam System System Trim Section FM 0723 0 09 A Trim Schematic System with electric release...

Страница 28: ...heck valve B9 Water pneumatically actuated control valve N C B10 Water supply control valve B11 Priming pressure water gauge valve B12 Water supply presure gauge valve B13 Clapper check valve B14 Flow...

Страница 29: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System System Trim Section FM 0723 0 09 A...

Страница 30: ...o protective caps have to be removed and most importantly no tubing or fittings are required to be installed after receiving The cylinders bank is also provided with a refilling outlet C9 which allows...

Страница 31: ...rs must be recharged by FireFlex or its trained authorized agent Contact FireFlex After Sales Support Department for information about the nearest authorized agent to your location 5 Maintenance and i...

Страница 32: ...23 0 12 B Figure 2 Compressed Air Cylinders Bank Rack mounted Air supply Components C1 Cylinders rack C2 Compressed air cylinder C3 Safety release disk C4 Cylinder valve C5 Pressure regulator C6 Press...

Страница 33: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System Air Supply Section FM 0723 0 12 B This page is left blank intentionally...

Страница 34: ...For further details see the Foam Concentrate Data Sheet Environmental and Toxicological Information Foam concentrates used with Compressed Air Foam Systems are biodegradable However as with any subst...

Страница 35: ...tube is drained CLOSE tank drain valve T3 both sight gauge isolation valves T4 and the tank refill vent valve T6 b If level is below normal add foam concentrate up to normal level by following FILLIN...

Страница 36: ...en from the Storage tank drain valve T3 Foam samples may be sent to FireFlex Systems Either glass or plastic bottles are satisfactory provided they are leak proof and well packaged The sample s must b...

Страница 37: ...approximately 1 minute or until pressure stabilizes at the Foam injection line pressure gauge F4 4 CLOSE foam injector flushing valve F5 5 Foam injection line pressure gauge F4 should vent quickly and...

Страница 38: ...13 D Figure 2 Foam storage tank schematic Foam storage tank components T1 Foam storage tank T2 Dip tube T3 Storage tank drain valve T4 Level sight gauge isolation valve T5 Foam level sight gauge T6 Fo...

Страница 39: ...Page 6 of 6 ICAF Integrated Compressed Air Foam System Foam Supply Section FM 0723 0 13 D This page is left blank intentionally...

Страница 40: ...on system auxiliary contacts and signaling devices Knockouts can be drilled by the installing contractor on site but have to meet the restrictions indicated on Figure 2 Gauges to indicate air water su...

Страница 41: ...te to access anchoring holes 2 MAX W SIZE VARIES ACCORDING TO MIXING CHAMBER SIZE SCH 40 GROOVED OUTLET MIXING CHAMBER 1 MIXING CHAMBER 2 SCH 40 GROOVED OUTLET OPTIONAL OUTLET DRILLED ONLY WHEN 2 nd M...

Страница 42: ...only to avoid internal components and about 1 2 from cabinet rear edge as shown 5 3 9 15 FM 072C 0 251 B dwg Wiring Routing Wiring shown in Figure 3 below indicates typical Wiring Routing for Power Li...

Страница 43: ...Page 4 of 4 ICAF Integrated Compressed Air Foam System System Characteristics Section FM 0723 0 14 C This page is left blank intentionally...

Страница 44: ...Page 1 of 2 ICAF Integrated Compressed Air Foam System Notes Warranty FM 0723 0 16 B User Notes...

Страница 45: ...ow long an expressed warranty lasts so the above limitations may not apply to you Under no circumstances shall the Manufacturer be liable for any loss of or damage to property direct or indirect incid...

Отзывы: