INSTALLATION REQUIREMENTS

If the appliance is to be sited near a disused natural draught flue it is recommended that the old flue
should be partially sealed off to prevent draughts, however some ventilation will be required to prevent
condensation. The appliance is designed to be wall mounted. It is possible to install the appliance onto
certain types of combustible materials - see section entitled ‘Clearances to combustible materials’.
In the event that the fire is sited near a disused or unserviceable fireplace served by a natural draught
flue, any existing under grate draught device should be sealed off to prevent loss of heat or creation of
draughts. The passageway into the flue should be partially sealed to prevent excessive draughts, however
some ventilation will be required in the old flue to prevent condensation and dampness. Advice should be
sought from your local building control officer.

ROOM SIZING

The room size should be a minimum of 23m3 (e.g. 10’2” x 10’2” x 8’) to allow adequate circulation of air
and ensure the correct operation of the fire. This volume may include adjacent spaces but these spaces
must not be separated by a door. To calculate a room size in cubic metres (m3) divide the room volume
in cubic feet (ft3) by 35.3. 

SITE REQUIREMENTS

This appliance is designed to be wall-hung. Do not recess any part of the appliance into the wall.

This Appliance may be installed in any room in a home, however there are exceptions, and the appliance
may not be used in the following rooms;

· Bedrooms - or areas which are mainly used for sleeping.
· Bathrooms - or areas where large amounts of steam are likely to be generated.

Installation in living rooms is common, however other rooms such as kitchens, dining rooms and hall-
ways are permitted, providing a suitable natural gas supply is available, and rooms sizing and ventilation
requirements are strictly adhered to (see section 4.1).

The appliance is designed to be versatile, and as such will operate correctly when exposed to normal gen-
tle draughts experienced within the home. It is not recommended, however that the appliance be installed
in areas where it is likely to be exposed to persistent strong draughts, that may be generated by outside
doors or windows, air vents etc. It is recommended that the appliance should not be installed within 500mm
of any air vent.

2

APPLIANCE DATA

Gas Group

G20 Natural Gas CAT I2H

Inlet Pressure

20 mbar

Max Energy Input 

Gross

2.0 kW

Net

1.8 kW

Max Gas Rate

0.20 m3/h

Min Energy Input 

Gross

1.3 kW

Net

1.15 kW

Pilot Energy Input 

Gross

166 W

Net

150 W

Burner Pressure High

17.3 mbar. (+/-0.75 mbar). Hot
17.0 mbar. (+/-0.75 mbar). Cold

Low

6.3 mbar. (+/-0.25 mbar). Hot
6.0 mbar (+/-0.25 mbar). Cold

Main burner flow restrictor

Stereo 1.03mm (1/4” BSP)

Oxypilot

SIT/Bray 9082

Gas Inlet Connection

8mm inlet restrictor elbow

Ignition

Piezo spark

Spark Gap

4.0 mm (± 1.0mm)

Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.

2.0

3.0

3.1

4.0

Содержание L23G

Страница 1: ...EL LE ES SS S G GA AS S F FI IR RE E M MO OD DE EL L L L2 23 3G G I IN NS ST TA AL LL LA AT TI IO ON N A AN ND D U US SE ER R I IN NS ST TR RU UC CT TI IO ON NS S All instructions must be handed to u...

Страница 2: ...FL05 FL06...

Страница 3: ...d by a door In order to convert from cubic feet ft3 to cubic metres m3 divide the room vol ume in ft3 by 35 3 This appliance is intended as a secondary source of heat only and should not be used in a...

Страница 4: ...only in a suffi ciently ventilated space A minimum of 100cm2 15 5 in2 purpose provided ventilation is required for this appliance an openable window or louvre is also required To reduce the possibilit...

Страница 5: ...a home however there are exceptions and the appliance may not be used in the following rooms Bedrooms or areas which are mainly used for sleeping Bathrooms or areas where large amounts of steam are l...

Страница 6: ...positioned on the wall above the appliance The appliance is designed to be wall mounted alone and not in conjunction with any type of combustible fire surround No combustible shelves should be positi...

Страница 7: ...e gas supply pipework to enter the appliance firebox These entry points are knock out type holes Non concealed gas connections may be made using the entry points at either end of the firebox or the on...

Страница 8: ...tely 5mm from the wall Now hang the appliance onto these screws through the two keyhole shaped holes in the back panel of the appliance Insert the lower fixing screws into the lower wall plugs through...

Страница 9: ...f under any circumstances the piezo electric spark fails the pilot can not be lit manually SETTING PRESSURE The pressure test point is located on the left hand side of the appliance on the main burner...

Страница 10: ...n in order to create a 2mm gap shown Simply hang the facia panel onto the outer casing ensuring that the corresponding keyhole shaped holes engage the screw heads fully BRIEFING THE CUSTOMER All instr...

Страница 11: ...main burner pipes and blow through to dislodge any debris Now remove the restric tor elbow and blow through to make sure it is entirely clear Unclip the pilot lint gauze and clean with a soft brush Cl...

Страница 12: ...gure by 10 000 Examples 35ppm 0 0035 15ppm 0 0015 5ppm 0 0005 Now divide the concentration of carbon monoxide CO expressed in percent by the concentration of car bon dioxide CO2 to obtain the applianc...

Страница 13: ...tray realign HT lead Fire runs for a time and then cuts off Loose or faulty thermocouple rectify Blocked pilot clean out Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If th...

Страница 14: ...bracket Combustible items such as flooring and furniture and soft wall coverings such as blown vinyl or embossed paper low temperature surrounds etc may discolour if fitted too close to the fire See...

Страница 15: ...or discolouration may occur over time The appliance must not be positioned vertically within 100 mm of a carpeted floor rugs or fabric materi als of any kind This dimension is measured vertically to t...

Страница 16: ...or or window has been opened cre ating a draught then pilot disturbance could be the problem and removal of the draught should resolve this The appliance can then be re lit in accordance with the prev...