APPENDIX A – NETWORK INSTALLATION TIPS

1. Network wires must remain in pairs.

The most important item to remember when installing a pantherC series network 
system is to keep the network wires as a pair; retaining a close proximity between 
the two conductors. A twisted pair is preferred, but not required. When using a 
terminal block, connect the wire pair to terminals directly next to each other. 
When passing through collector rings or other similar devices, use conductors that
are next to each other.

2. Network spurs are not permitted.

A network pair from one unit to the next, or to a terminator, should contain only 
the two wires running directly between units with no spur routes or additional 
wires spliced into the run. The units in a network are connected in series. When
retrofitting a pantherC series system into a previously installed wiring system, it is 
important to trace the wiring and confirm that no additional wires have been 
spliced into the intended network wires.

3. Identical wire treatment.

Both wires of a network pair should be treated identically. The wires should be of 
equal length and terminated in the same manner. If one wire is connected at a 
block or in-line splice, the other wire of the pair should be connected at the same 
point and in the same manner, keeping the wires close together. When retrofitting
a system into a previously installed wiring system, it is important to trace the wiring 
and confirm that both conductors of the wire pair are of equal length and treated 
identically.

4. Avoid non-essential splices.

When possible, avoid splices on the network. When splices or termination is 
required, make sure both wires of the pair are treated identically.

5. Ground shields at one end only.

Cable shielding is recommended but not required. When using shielded cable, 
ground the shield at one end of the cable only.

6. Avoid bundling excess wire.

Excess network wire should be removed and not bundled. Sharp bends or kinks 
in network wire can be harmful. Typical minimum bend radius for network wiring 
is in the 2 to 3 inches range. See cable manufacturer for recommended minimum 
bend radius.

7. Avoid 3-phase power cables and fluorescent lights.

Keep all network wires 1 foot away from 3-phase power and fluorescent lights. 

APPENDIX A – NETWORK INSTALLATION TIPS

Connecting Network Units

Never splice into network wires. All units come with network in and out connections.
Wire all units in series with terminators at both ends.

Direct Network Wiring

Do not bundle excess network wiring. Choose direct routes for network cables and
remove all excess cable.

DO NOT

Splice additional wires into network cables

DO 

Connect using 2-conductor connectors

DO NOT

Bundle excess cable

DO

Cut cables to length

Содержание pantherC Series

Страница 1: ...nd Oregon 97224 800 527 0555 503 684 6647 Fax 503 620 2943 Email sales firecom com www firecom com Copyright 2008 Sonetics Corporation All rights reserved The information in this document is subject t...

Страница 2: ...rview 2 Features 3 Intercom Models 4 Installation 4 5 Wire Connections 6 System Wiring 7 8 Operation 9 Troubleshooting 10 11 Options and Accessories 12 Maintenance 13 AppendixA NetworkInstallationTips...

Страница 3: ...l fully informed by monitoring radio traffic In addition all positions on the pantherC series have radio transmit capability by using a Firecom series 10 headset with red PTT button WARNING Safety Inf...

Страница 4: ...TION Mounting and Overall Dimensions swivel mount bracket included Both an adjustable swivel style mounting bracket and two angle brackets are provided A flush mount bracket is also available see Opti...

Страница 5: ...he second unit The negative network wires are connected similarly Network wires between units must remain paired in a 2 conductor or more cable Twisted pair wiring is preferred but not required for al...

Страница 6: ...disengage the remote unit microphone when sent via a panel PTT button An automatic gain control is provided for every remote and base unit microphone When extremely high noise is present the transmitt...

Страница 7: ...disconnect it Be sure to press the PTT button when talking from a base unit If you are trying to talk on a remote unit be sure you are speaking loudly enough to activate the voice activated microphone...

Страница 8: ...s well as talk to anyone on a Firecom 30XXR intercom HE 150 Part No 108 0675 15 15 coiled headset extension cable for use with any single plug headset for greater mobility at pump panel position Netwo...

Страница 9: ...int and in the same manner keeping the wires close together When retrofitting a system into a previously installed wiring system it is important to trace the wiring and confirm that both conductors of...

Страница 10: ...e to a safe level for the environment in which the intercom is being used or use Firecom headsets to reduce noise 17 16 APPENDIX A NETWORK INSTALLATION TIPS 8 Impedance mismatches are harmful The pant...

Отзывы: