WIRE CONNECTIONS

CABLE (PROVIDED)

Wire Color          Designation
   GRY                Power (-)
   YEL                 Power (+)
   DRAIN             Chassis Gnd
   WHT                Net (-)
   GRN                Net (+)
   BLU                 Net (-)
   BRN                 Net (+)

Power

12 VDC (2.5 amps maximum)
A 5 amp fuse is required

Wire Size

Power:

18 gauge min.

Network: 

22 gauge min. 

(Shielded twisted pair cable is 
recommended but may not be 
required for all installations.)

SYSTEM WIRING

Over 100 devices can operate on one network, but only 8 full-duplex conversations
can occur simultaneously. 

The 2-wire network is connected by wiring intercoms in series. The positive network
wire of one unit is connected to the positive network wire of the second unit. The
negative network wires are connected similarly. Network wires between units must
remain paired in a 2 conductor or more cable. Twisted pair wiring is preferred but
not required for all installations. Both two unit wiring and multiple unit wiring are
shown below. The ends of a network are always completed with a terminator.

The following are recommendations for all installations:
(Also see Appendix A – Network Installation Tips).

• 

Use Belden 9463 Twinaxial cable when possible.

• 

Keep network wire pairs together at all times.

• 

Connect network units in series.

• 

Do not splice additional wires into network cable runs.

• 

Do not bundle excess network cable.

Two Unit Wiring

WHT

GRN

TERMINATOR

BLU

BRN

WHT

GRN

TERMINATOR

BLU

BRN

YEL (+)

GRY (-)

DRAIN (CHASSIS GND)

POWER

DRAIN (CHASSIS GND)

POWER

YEL (+)

GRY (-)

Содержание pantherC Series

Страница 1: ...nd Oregon 97224 800 527 0555 503 684 6647 Fax 503 620 2943 Email sales firecom com www firecom com Copyright 2008 Sonetics Corporation All rights reserved The information in this document is subject t...

Страница 2: ...rview 2 Features 3 Intercom Models 4 Installation 4 5 Wire Connections 6 System Wiring 7 8 Operation 9 Troubleshooting 10 11 Options and Accessories 12 Maintenance 13 AppendixA NetworkInstallationTips...

Страница 3: ...l fully informed by monitoring radio traffic In addition all positions on the pantherC series have radio transmit capability by using a Firecom series 10 headset with red PTT button WARNING Safety Inf...

Страница 4: ...TION Mounting and Overall Dimensions swivel mount bracket included Both an adjustable swivel style mounting bracket and two angle brackets are provided A flush mount bracket is also available see Opti...

Страница 5: ...he second unit The negative network wires are connected similarly Network wires between units must remain paired in a 2 conductor or more cable Twisted pair wiring is preferred but not required for al...

Страница 6: ...disengage the remote unit microphone when sent via a panel PTT button An automatic gain control is provided for every remote and base unit microphone When extremely high noise is present the transmitt...

Страница 7: ...disconnect it Be sure to press the PTT button when talking from a base unit If you are trying to talk on a remote unit be sure you are speaking loudly enough to activate the voice activated microphone...

Страница 8: ...s well as talk to anyone on a Firecom 30XXR intercom HE 150 Part No 108 0675 15 15 coiled headset extension cable for use with any single plug headset for greater mobility at pump panel position Netwo...

Страница 9: ...int and in the same manner keeping the wires close together When retrofitting a system into a previously installed wiring system it is important to trace the wiring and confirm that both conductors of...

Страница 10: ...e to a safe level for the environment in which the intercom is being used or use Firecom headsets to reduce noise 17 16 APPENDIX A NETWORK INSTALLATION TIPS 8 Impedance mismatches are harmful The pant...

Отзывы: