EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN 

 

 

 

 

PUBLICATION:

  

FIRECLASS PREC EN INST

 

 

 

 

 

ISSUE No. & DATE:

 

3      13/09/18

 

PAGE 24 of 30 

 

SW 1/5 - Config I/S Zones:  

o

  OFF: Configuration mode disabled. 

o

  ON:  Enables  selected  zones  to  be  configured 

to  Intrinsically  Safe  alarm  thresholds  and 
passive  end  of  line  fault  monitoring  via  the 
Engineer’s  Select  feature.  [For  use  with 
appropriate I.S. barriers/Isolators, typically 330 
Ohm zener barriers or galvanic isolators].  

[Not EN54 compliant function.] 

 

 

SW 1/6 - Config M/S Zones:  

o

  OFF: Configuration mode disabled. 

o

  ON:  Enables  selected  zones  to  be  configured 

to  short  circuit  fire  mode  via  the  Engineer’s 
Select feature. 

 

 

SW 1/7 - Config Delay Zones:  

o

  OFF: Configuration mode disabled. 

o

  ON:  Enables  selected  zones  to  be  configured 

to  Delay  Mode  via  the  Engineer’s  Select 
feature. 

 

 

SW 1/8 - Configure Delay O/Ps:  

o

  OFF: Configuration mode disabled. 

o

  ON:  Enables  the  selection  of  outputs,  via  the 

Engineer’s  Select  feature,  to  which  the  panel 
delay will apply. 

 

 

SW 1/9 - 2 Stage Delay:  

o

  OFF: Single Stage Delay Mode. 

o

  ON: Two Stage Delay Mode. 

 

 

SW 1/10 - Alarms on Evac Only:  

o

  OFF:  Sounders  operate  on  any  fire  condition 

including evacuate. 

o

  ON:  Selects  sounders  to  operate  only  when 

the panel is in the evacuate condition. 

Not EN54 complaint function. 

 

 

SW 2/1 - Silence Before Reset:

  

Select  type  of  reset  mode.  [Not  EN54  compliant 
function.  Provided  to  meet  existing  customer 
requirements]: 

o

  OFF: Reset available when panel is in the [un-

silenced] fire or fault condition. 

o

  ON:  Fire  Condition  Reset  available  only  when 

panel  is  in  Alarm  Silenced  condition.  Fault 
reset  available  when  panel  is  in  the  fault 
condition. 

 

 

SW 2/2 to 2/5 - Delay/Minutes:

  

Sets the duration of the variable time delay element 
[i.e.  the  single  stage  delay  and  stage  2  of  the  two 
stage delay] in steps of 1 minute within the range 0-

9  minutes.  See  Table  1 

–  Motherboard  Delay 

Switch Settings 

Table 1 

– Motherboard Delay Switch Settings 

Delay 

Duration 

S/W 

2/2 

S/W 

2/3 

S/W 

2/4 

S/W 

2/5 

Delay disabled 

Off 

Off 

Off 

Off 

1 min 

On 

Off 

Off 

Off 

2 min 

Off 

On 

Off 

Off 

3 min 

On 

On 

Off 

Off 

4 min 

Off 

Off 

On 

Off 

5 min 

On 

Off 

On 

Off 

6 min 

Off 

On 

On 

Off 

7 min 

On 

On 

On 

Off 

8 min 

Off 

Off 

Off 

On 

9 min 

On 

Off 

Off 

On 

10 min 

Off 

On 

Off 

On 

 

On 

On 

Off 

On 

 

Off 

Off 

On 

On 

 

On 

Off 

On 

On 

 

Off 

On 

On 

On 

 

On 

On 

On 

On 

 

SW 2/6 - Enable Zonal Alarms:

  

Select  the  type  of  sounder  alarm  response  to  a 
fire  condition  in  conjunction  with  the  Pulse  Non 
Alarm  Zones  switch  described  below.  [Not  EN54 
compliant  function.  Provided  to  meet  existing 
customer requirements]: 

o

  OFF:  General  Alarm  Mode  -  all  sounders 

operate continuously until silenced. 

o

  ON: Zonal Sounder Mode - Sounder groups for 

zones  not  in  the  alarm  condition  may  be 
selected,  via  the  Pulse  Non  Alarm  Zones 
switch [SW 2/7], to pulse or not to operate. 

Note:  Zonal  alarms  on  the  2/4  zone  panel  affects 
the standard sounder circuits on the motherboard. 
On  the  8,  16  and  32  zone  panels,  it  affects  only 
the [future] expansion module sounder circuits. 

 

 

SW 2/7- Pulse Non Alarm Zones:

  

Select  the  type  of  zonal  sounder  alarm  response 
to  a  fire  condition  in  conjunction  with  the  Zone 
Alarms  switch  [SW  2/6]  described  above.  [Not 
EN54  compliant  function.  Provided  to  meet 
existing customer requirements]: 

With  the  Zone  Alarms  switch  [SW  2/6]  in  the  On 
position [Zonal Sounder Mode]: 

o

  SW2/7  OFF:  Zonal  sounders  for  zone  in  the 

fire  condition  operate  continuously  until 
silenced. All others are silent.  

o

  SW2/7 

ON: 

Zonal 

sounders 

operate 

continuously  -  all  other  sounders  operate  in 
pulsed mode until silenced.  

 

Содержание Precept EN 16

Страница 1: ...PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 1 of 30 Johnson Controls Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland Precept EN Fire Detection Alarm Panel P...

Страница 2: ...15 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 23 15 5 INVALID CONFIGURATION CONDITIONS 23 15 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR FUNCTIONS 23 15 7 CONFIGURABLE OPTIONS VIA DIL...

Страница 3: ...eps that are taken in designing installing and commissioning a FIRECLASS Precept EN system 1 Install all field wiring and equipment Refer to the Installation Guidelines in section 11 2 below Refer to...

Страница 4: ...h label C1631 repeater interface optional J18 B Figure 3 Precept EN 32 Zone Internal View TB 1 30 J 1 J 1 TO MOTHERBOARD 25 TB 2 26 27 TB 3 18 17 19 TB 5 28 TB 4 29 TB 6 ZONE CIRCUITS 20 21 22 TB 8 31...

Страница 5: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 5 of 30 Figure 4 2 4 Zone Precept EN panel General Assembly with optional clock module...

Страница 6: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 6 of 30 Figure 5 8 16 Zone Precept EN panel General Assembly with optional clock module...

Страница 7: ...EQUIPMENT FIRECLASS PRECEPT EN PUBLICATION FIRECLASS PREC EN INST ISSUE No DATE 3 13 09 18 PAGE 7 of 30 Figure 6 32 Zone Precept EN panel General Assembly with optional clock module...

Страница 8: ...nnect to Aux DC 24V 24V DC relay Typical zonal output wiring Field relay spec Coil resistance 2 6K to 4 5K Ohms Voltage 24V DC Nom min 18V max 30V Fitted with suppression diode as shown Relay local to...

Страница 9: ...A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement active EVAC Evacuation active BUZ Active Buzzer active Class change Buz Active Lower terminal tier Upper te...

Страница 10: ...LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Connector for C1632 Zone Expansion Board...

Страница 11: ...denoting any one of the following conditions a Battery or associated wiring disconnected b Battery fuse blown c Low Battery voltage 15 7V 0 4V d Battery and interconnection resistance is equal to or...

Страница 12: ...ne Panel Power Supply Layout Secondary AC Supply from Transformer 28V 0V DC Power output Mains Fault Output Common Fault Output 4 way header for connector to 32 zone motherboard for DC power common fa...

Страница 13: ...care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery...

Страница 14: ...h contain PCBs with sensitive and fragile electronic components on them You must place them in an area that is clean dry and dust free where they will not be damaged You can place them inside the orig...

Страница 15: ...igure 10 Figure 12 Fit the connector on the end of the black lead onto the negative black terminal of the left hand battery Fit the connector on the end of the red lead onto the positive red terminal...

Страница 16: ...s and field devices to check each circuit and function in turn to ensure correct operation of the entire system In this way any faults may be located quickly and accurately The general procedures are...

Страница 17: ...and the battery is OK the panel should be silent displaying only the Power Supply On indication 5 Turn the Access Keyswitch to 1 and press the Test Display button The panel should respond by lighting...

Страница 18: ...ue to test each of the other detectors in turn checking on each removal that The appropriate amber zone fault LED illuminates The internal buzzer sounds The fault relay operates 5 Repeat steps 1 to 4...

Страница 19: ...At Repeater 1 turn the Access control switch to 1 and press the Evacuate button Check that the alarms operate and the internal buzzer operates on all repeaters 3 Press the Silence button on the fire a...

Страница 20: ...ult Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SUPPLY FAULT SYSTEM FAULT...

Страница 21: ...and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1 de...

Страница 22: ...anel door to allow access to the buttons on the display 2 Select a zone or output to be configured o On the panel display press the Select On Off switch to enable the Select Mode The Select LED will b...

Страница 23: ...onfig LED on the motherboard will flash o The System Fault and Select LEDs on the display will flash o The fault relay will operate o The panel buzzer will sound o The Cursor indication will clear o C...

Страница 24: ...es Sets the duration of the variable time delay element i e the single stage delay and stage 2 of the two stage delay in steps of 1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Sw...

Страница 25: ...ff Off On 5 On Off On Note Address 0 repeater disabled 15 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove...

Страница 26: ...DISABLE to change MM to desired value 00 to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Ti...

Страница 27: ...Settings LINK 1 Position Function Fitted 1st fire alarm time display mode Removed Day Night mode Link 1 DIL Switch 1 DIL Switch Position Function Off 1 Off Clock Module menu configuration disabled 1...

Страница 28: ...ulses every second WP DILSW IS ON The backlight remains OFF The panel indicates a general fault and prevents the clock module from being accessed by the user engineer 16 4 2 EEPROM Error Message Data...

Страница 29: ...250V 1A anti surge T1A H250V 1A anti surge T1A H250V 1A anti surge Voltage 230V AC 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Precept EN P...

Страница 30: ...ff PS1230 2V 3 4Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 133 W 67 H 60 HT 66 L 151 W 65 H 94 HT 98 L 151 W 98 H 94 HT 100 L 181 W 76 H 167 HT 167 L 133 W 67 H 60 HT 66 L 133 W 67 H 60 HT 6...

Отзывы: