FireClass
FC410MIO
Fixing Instructions
Doc. version 6.0
7/16
Note:
This device uses one address only on the
loop (in the case of FireClass Express, 7 addres-
ses will be used).
Cabling
Cables are to be selected in accordance with the
system design document and the requirements
of the applicable standards.
Two pairs of connection terminals (L+ and L-) are
provided on the terminal block. These terminals
are used for connecting the module onto the
addressable circuit. The maximum section of
the cable that can be connecte at any one termi-
nal is 2.5mm
2
. The section is calculated based
on the characteristics of the cable and the load.
Ordering information
FC410MIO: Small Addressable Multi-I/O
Module.
Recycling information
Customers are recommended to dispose of their
used equipments (panels, detectors, sirens, and
other devices) in an environmentally sound man-
ner. Potential methods include reuse of parts or
whole products and recycling of products, com-
ponents, and/or materials.
Waste electrical and electronic
equipment (WEEE) directive
The manufacturer reserves the right to change
the technical specifications of this product
without prior notice.
Note:
1 All SPUR inputs must be terminated with a
330 ohm EOL resistor.
2 FireClass console or FireClass Express confi-
guration selection- Style B (Normally Open).
3 *Multiple contacts may be used as needed.
Notes:
1 For connection of HVR800s, refer to docu-
ment HVR800 High Voltage Relay Module
“Installation Instructions” 17A-03-HVR, Issue
3 or later, or 120.415.528, Issue 5 or later.
2 Relay wiring will be application dependant;
refer to the system diagram.
In the European Union, this label indi-
cates that this product should NOT
be disposed of with household
waste. It should be deposited at an
appropriate facility to enable
recovery and recycling.
WARNING
The FC410MIO must not be used
to switch mains voltages.
CENTRALE FC
FC CONTROLLER
+L1
-L1
03
3
ET
NE
U
GE
S
OVI
TI
S
OP
SI
D
L
A
E
CI
VE
D
TX
E
N
OT
03
3
03
3
NC
NO
*
NC
NO
*
NC
NO
*
INGRESSI SPUR
SPUR INPUTS
PROGRAMMING PORT
PORTA DI PROGRAMMAZIONE
LEFT
HVR800-Treiber
HVR800-Drivers
FC410MIO
Fig. 5: Spur Circuit (Class B) Normally Open
Contacts, Short Circuit = Alarm