Fixing Instructions

Doc. version 6.0

5/16

STYLE B - Monitor multiple normally open 
contacts with a short on the zone giving an 
alarm.

 STYLE C - Monitor a single normally open or 
normally closed contact with a short or open 
on the zone, giving a fault.

Features

The FC410MIO monitoring and control features 
include the following configurable items.

 Addressable functionality.

 Monitoring three Class B circuits either 
normally open or normally closed contacts.

 The status of the identified monitored 
contact signals to the Fire Controller.

 The status of the wiring to the relay contacts.

 The LED lights when a contact, on any of 
three monitored zones, has switched to the 
active (off normal) state.

 The LED when normally off, will pulse when 
the FC410MIO is polled by the controller.

Note:

1 All  SPUR  inputs  must  be terminated with a 

330 ohm EOL resistor.

2 FireClass console or FireClass Express confi-

guration selection - Style C (Normally Open).

3 One contact for each SPUR circuit.

Notes:

1 For connection of HVR800s, refer to 

document HVR800 High Voltage Relay 
Module “Installation Instructions” 17A-03-
HVR, Issue 3 or later, or 120.415.528, Issue 5 
or later.

Fig. 1: FC410MIO Small addressable multi-I/O 
module

INGRESSI SPUR

SPUR INPUTS

HVR800-Treiber

HVR800-Drivers

FC410MIO

PORTA DI PROGRAMMAZIONE

PROGRAMMING PORT

ANSCHLUSSBUCHSEN FÜR

HANDPROGRAMMIERGERÄT FC490ST

Fig. 2: FC410MIO PCB Layout

PROGRAMMING PORT

PORTA DI PROGRAMMAZIONE

CENTRALE FC

FC CONTROLLER

ET

NE

U

GE

S

OVI

TI

S

OP

SI

D

L

A

E

CI

VE

D

TX

E

N

OT

T

NE

ME

LE

NE

TS

H

C

Ä

N

M

UZ

INGRESSI SPUR

SPUR INPUTS

EINGÄNGE

STICHLEITUNGEN

Ringleitung

HVR800-Treiber

HVR800-Drivers

FC410MIO

L1

FC

L1

LEFT

Fig. 3: SPUR circuits (Class B) Normally Open Con-
tacts, Short Circuit = Fault.

Содержание 555.800.765

Страница 1: ...Stichleitung St rung bei Kurzschluss ffner Die LED leuchtet wenn einer der drei Eing nge aktiviert ist Technische daten Elektrische daten Adresseinstellung Im Auslieferungszustand ist die Adresse stan...

Страница 2: ...y GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland 09 DoP 2015 4017 EN54 18 Input output device for fire detection and fire alarm systems for buildings FC410MIO Essential Chara...

Страница 3: ...onsweise der Relaisausg nge PROGRAMMING PORT PORTA DI PROGRAMMAZIONE CENTRALE FC FC CONTROLLER E T N E U G E S O V I T I S O P S I D L A E C I V E D T X E N O T T N E M E L E N E T S H C N M U Z INGRE...

Страница 4: ...tage Relay Modules can be individually driven and controlled by an FC410MIO if all HVR800s are powered by 24V dc or 24V ac In this application the HVR800s are controlled by the two latching relays on...

Страница 5: ...the controller Note 1 All SPUR inputs must be terminated with a 330 ohm EOL resistor 2 FireClass console or FireClass Express confi guration selection Style C Normally Open 3 One contact for each SPUR...

Страница 6: ...e backbox using the screws and stand offs supplied Note 1 All SPUR inputs must be terminated with a 330 ohm EOL resistor 2 FireClass console or FireClass Express configuration selection Style C Normal...

Страница 7: ...trical and electronic equipment WEEE directive The manufacturer reserves the right to change the technical specifications of this product without prior notice Note 1 All SPUR inputs must be terminated...

Страница 8: ...IO se i moduli HVR800 sono alimentati a 24 Vcc o 24 Vac In questa applicazione i moduli HVR800 sono controllati dai due rel bistabili del modulo FC410MIO Un massimo di quattro rel ad alto voltaggio HV...

Страница 9: ...o FC410MIO viene interrogato dalla Centrale Note 1 A tutti gli ingressi SPUR v collegato un resis tore EOL da 330 ohm 2 Selezionare Stile C Normalmente Aperto in FireClass console o FireClass Express...

Страница 10: ...a zione del Rel ad Alto Voltaggio HVR800 17A 03 HVR revisione 3 o superiore oppure 120 415 528 revisione 5 o superiore Montaggio Per montare il modulo FC410MIO nella scatola elettrica procedere come s...

Страница 11: ...2 5 mm2 La sezione v calcolata in base alle caratteristiche del cavo e del carico Informazioni per l ordine FC410MIO Modulo 3 Ingressi 4 Uscite Informazioni sul riciclaggio Si consiglia ai clienti di...

Страница 12: ...contatti se necessario Note 1 Per il collegamento dei moduli HVR800 con sultare il documento Istruzioni di Installa zione del Rel ad Alto Voltaggio HVR800 17A 03 HVR revisione 3 o superiore oppure 120...

Страница 13: ...s de blo queo Las entradas de clase B pueden supervisar los contactos de un sistema de incendios como el control del sistema de extinci n el control de la ventilaci n el control de las puertas antiin...

Страница 14: ...ntrolador de incendios Indicaci n del estado del cableado a los con tactos de rel El LED se ilumina cuando un contacto de cual quiera de las tres zonas supervisadas cambia al estado activo fuera del e...

Страница 15: ...s en los esquemas Nota Este dispositivo solo utiliza una direcci n en el bucle en el caso de FireClass Express se utilizan 7 direcciones Cableado Los cables se deben seleccionar de acuerdo con el docu...

Страница 16: ...330 330 0 3 3 NC NO NC NO NC NO FC410MIO Puerto de programaci n Al siguiente dispositivo Izquierda Central de control Entradas de ramal Controladores del HVR800 Fig 4 Circuitos de ramal clase B conta...

Отзывы: