Operation 

 

OK

” LED On = system is all ok.

 

 

FAULT

” LED On = either 

open or shorted smoke detection cable or sensor. 

 

If there is a short on the line: 

If a short is detected on the line the “OK “LED will turn 

off

, the “FAULT” LED and

 alarm 

will turn on, the Sensor Output will also be turned off. When the 

“SILENCE / RESET 

button 

is pushed the “FAULT” LED will turn 

off and the zone 

“OK” LED will flash for one 

minute, after the one minute delay the Sensor Output will turn on again to check the line. 
This procedure will repeat until the short is removed. 
 

If the line is open circuit: 

If an open circuit is detected on the line the “OK“

 LED will turn off

, the “FAULT” LED

 and 

alarm will turn on. When the “SILENCE/RESET“

 button is pushed the alarm will be 

muted. 

When the system detects the EOL resistor the “FAULT” LED will turn off

 and the 

“OK” LED will turn on.

 

 

FIRE

” LED On = A sensor has detected smoke or heat.

 

 

SILENT / RESET

 Button: 

This button will mute the audible alarm and reset the sensors. 
 

TEST

 Button: 

If the TEST button is pressed for three seconds the unit will go into Test mode. 

All LED’S and the alarm will turn 

on for five seconds. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

Electrical Specifications FR-1000/2000 
 

Minimum (alarm current) = 10mA 
Operate voltage = 9 - 30vdc 
Maximum current per zone = 320mA (including EOL) 
Siren/Buzzer output = 12vdc @ 800mA 

 
Supply voltage @ 12vdc 
Maximum sensors = 14 per zone 
Must use 2k2 EOL resistor 
 
Supply voltage @ 24vdc 
Maximum sensors = 8 per zone 
Must use 5k6 EOL resistor 

 