7
Operation
“
OK
” LED On = system is all ok.
“
FAULT
” LED On = either
open or shorted smoke detection cable or sensor.
If there is a short on the line:
If a short is detected on the line the “OK “LED will turn
off
, the “FAULT” LED and
alarm
will turn on, the Sensor Output will also be turned off. When the
“SILENCE / RESET
“
button
is pushed the “FAULT” LED will turn
off and the zone
“OK” LED will flash for one
minute, after the one minute delay the Sensor Output will turn on again to check the line.
This procedure will repeat until the short is removed.
If the line is open circuit:
If an open circuit is detected on the line the “OK“
LED will turn off
, the “FAULT” LED
and
alarm will turn on. When the “SILENCE/RESET“
button is pushed the alarm will be
muted.
When the system detects the EOL resistor the “FAULT” LED will turn off
and the
“OK” LED will turn on.
“
FIRE
” LED On = A sensor has detected smoke or heat.
SILENT / RESET
Button:
This button will mute the audible alarm and reset the sensors.
TEST
Button:
If the TEST button is pressed for three seconds the unit will go into Test mode.
All LED’S and the alarm will turn
on for five seconds.
Electrical Specifications FR-1000/2000
Minimum (alarm current) = 10mA
Operate voltage = 9 - 30vdc
Maximum current per zone = 320mA (including EOL)
Siren/Buzzer output = 12vdc @ 800mA
Supply voltage @ 12vdc
Maximum sensors = 14 per zone
Must use 2k2 EOL resistor
Supply voltage @ 24vdc
Maximum sensors = 8 per zone
Must use 5k6 EOL resistor