16
3.5 Sizing Collector Area
There are various methods used to size a collector area. The guidance rule of thumb is 1m
2
per 50 litres storage.
The following formula provides a more accurate determination of the required collector area using local area
irradiation levels:
Collector area = Solar fraction x operational days x hot water energy requirement
(Ref: CIBSE)
Solar irradiation x system efficiency
The hot water energy requirement is calculated from the following equation:
E (hot water) = Daily Hot Water volume x 1.16 x
Δ
T
where 1.16 Wh/kg = specific heat capacity of water
Example:
E = (5x40) x 1.16 x (60-10) = 11,600 Wh/day
= 11.6 kW/day
Collector area = 60 x 365 x 11.6 = 4.7m
2
982 (Cork) x 55
The following table highlights irradiance values for various parts of Ireland and the UK:
(T*Sol Software)
Guidance values
The table below outlines guidance on number of persons to recommended collector areas and DHW tank sizes.
No. of persons
Number of collectors
Tank size (litres)
2 x CPK7210-N Flat Panel collectors
2-4
2 x CVSKC-10 Vacuum Tube collectors
200
30 or 40 TZ58-1800 heat pipes
3 x CPK7210-N Flat Panel collectors
5-6
3 x CVSKC-10 Vacuum Tube collectors
300
40 or 60 TZ58-1800 heat pipes
Ireland
UK
Location
(kW/m
2
a)
Location
(kW/m
2
a)
Bellmullet
929
Aboyne
866
Birr
899
Bangor Harbour
904
Claremorris
906
Bingley
926
Clones
880
Blackpool Airport
967
Cork Airport
980
Cambridge
964
Monaghan
904
Cardiff Wales
980
Dublin Airport
941
East Midlands
878
Kilkenny
983
Edinburgh
898
Malin Head
928
Guernsey Airport
1167
Mullingar
920
Isle of Man
1150
Roches Point
981
Leeds and Bradford
915
Shannon Airport
946
London Heathrow
956
Sligo Airport
899
Manchester
950
Valentia
982
Plymouth
1052
Belfast
906
Southampton
1087
Newry
898
Wallingford
945
Derry
907