Installation Guide
Step 1. Coarse Alignment
Refer to Figures 2 and 3 for this step.
1. Ensure that both of the optics lock-down screws are loosened so that the optics will move freely.
2. Looking through the alignment mirror, at both the alignment sight and reflector simultaneously, locate the
position of the reflector in the optical sight. This step will require some practice. It is necessary to train your
eyes to shift focus between the reflector and the mirror in order to locate the reflector. If the distance between
the reflector and the detector is large it is helpful to place a brightly coloured object on the wall near the
reflector to aid in seeing the reflector in the alignment mirror.
3. Once the reflector has been located, begin to adjust both the horizontal and vertical alignment knobs so that
the reflector becomes centred in the alignment mirror. Take care in this step. If the optics are incorrectly aligned
in this step, it will not be possible to proceed with the fine adjustment step.
3
Ensure that both the detector and reflector are mounted within their operational parameters for off axis
angles (see below)
3
Disable the zone or system to prevent unwanted alarms before applying power
3
Ensure power to the detector is “ON”
You are now ready to begin the alignment procedure.