SS-BEAM1224
Conventional Beam Detector
Installation Guide
PRODUCT DESCRIPTION
Installation/Alignment
The alignment is divided into four steps: coarse alignment, fine adjustment, final gain adjustment, and final
verification. It is necessary for all four steps to be executed properly to ensure proper alignment of the product.
Pre-Alignment Checklist
3
Ensure that both the detector and reflector are mounted securely to stable surfaces
3
Ensure that all wiring is correct
3
Ensure that terminal blocks are fully seated into their receptacles on the detector
3
Complete any wiring dressing to minimize movement to the detector once the alignment procedure is
completed
3
Ensure that the appropriate number of reflectors are used for the installed distance. Distances between
70 - 100m require additional reflectors (4 total). The BEAMLRK accessory should be used in these cases.
3
Ensure that the line of sight between the detector and reflector is clear and that reflective objects are not
too near.
TECHNICAL SPECIFICATIONS
Protection range
5m to 70m (70m to 100m long range kit)
Adjustment angle
± 10º horizontal and vertical
Sensitivity
(Refer to Sensitivity Chart on page
6 of Installation Guide)
Level 1 – 25% total obscuration
Level 2 – 30%
Level 3 – 40%
Level 4 – 50%
Acclimate Level 1 – 30-50%
Acclimate Level 2 – 40-50%
Alarm indicator
Local red LED and remote alarm
Trouble indicator
Local yellow LED and remote trouble
Normal indicator
Local flashing green LED
Temperature
-30ºC to 55ºC
Humidity
10% - 93% Relative humidity non-condensing
Voltage
10.2 to 32Vdc
Average standby current
17mA maximum
Alarm current
38.5mA maximum
Fault current
8.5mA maximum
Detector dimensions
254mm H x 191mm W x 84mm D
Reflector dimensions
5m to 70m 200mm x 230mm
Over 70m 400mm x 460mm