Installation of Optional Modules with Remote Accessories
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
4XTMF Transmitter Module
Push the disconnect switch to the down position to prevent accidental activation of the municipal box during test-
ing of the control panel. The Disconnect LED will remain illuminated while the municipal box is disconnected.
The System Trouble LED will indicate disconnected and/or open circuit conditions on the municipal box. During
trouble conditions, it is possible to obtain the circuit condition on the alarm reverse polarity output. If this opera-
tion is desired, cut the TBL jumper on the 4XTMF module.
!
Install 4XTMF Module by
plugging into connector
J6
and
J7
on MS-2410BC main board
Disconnect LED
Disconnect Switch
TBL Jumper
1 (+)
2 (-)
3 (+)
4 (-)
5
6 (+)
7 (-)
Remote Alarm (power-limited)*
Remote Trouble (power-limited)*
no connection
Municipal Box (nonpower-limited)*
* Wiring from these terminals can
exit the protected premises.
Cut JP1 for 4XTMF module
placement supervision
Polarities are shown for
module activation
FIGURE 2-17:
4XTMF Module Connections
MS-2410BC Main Circuit Board
4XTMF Module
Содержание MS-2410BC
Страница 6: ...6 Document 50801 Rev B 8 17 98 P N 50801 B MS 2410BC Terminals and Connectors AC Power ...
Страница 56: ...Slide in Labels 56 Document 50801 Rev B 8 17 98 P N 50801 B ...
Страница 58: ...Slide in Labels 58 Document 50801 Rev B 8 17 98 P N 50801 B ...
Страница 60: ...Slide in Labels 60 Document 50801 Rev B 8 17 98 P N 50801 B ...
Страница 61: ...Document 50801 Rev B 8 17 98 P N 50801 B 61 Notes ...
Страница 62: ...62 Document 50801 Rev B 8 17 98 P N 50801 B Notes ...
Страница 63: ...Document 50801 Rev B 8 17 98 P N 50801 B 63 Notes ...