Fire-Lite LDM-32F Скачать руководство пользователя страница 2

LimWarSm.p65    01/10/2000

An automatic fire alarm system

–typically made up of

smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning
of a developing fire.  Such a system, however, does not
assure protection against property damage or loss of life
resulting from a fire.

The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the
Guide for Proper Use of System Smoke Detectors, which
is made available at no charge to all installing dealers.
A study by the Federal Emergency Management Agency
(an agency of the United States government) indicated
that smoke detectors may not go off in as many as 35%
of all fires.  While fire alarm systems are designed to
provide early warning against fire, they do not guarantee
warning or protection against fire.  A fire alarm system
may not  provide timely or adequate  warning,  or  simply
may not function, for a variety of reasons:

Smoke detectors

 may not sense fire where smoke

cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors.  Smoke detectors also may not sense a fire on
another level or floor of a building.  A second-floor
detector, for example, may not sense a first-floor or
basement fire.

Particles of combustion or "smoke"

 from a developing

fire may not reach the sensing chambers of smoke
detectors because:

Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.

Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.

Smoke particles may be blown away from detectors
by air outlets.

Smoke detectors may be drawn into air returns before
reaching the detector.

The amount of "smoke" present may be insufficient to
alarm smoke detectors.  Smoke detectors are designed
to alarm at various levels of smoke density.  If such
density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have
sensing limitations.  Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires.  Because fires develop in different ways and are
often unpredictable in their growth, neither type of detec-
tor is necessarily best and a given type of detector may
not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smoking
in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time.  For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist.  

Heat

detectors are designed to protect property, not life.

IMPORTANT! 

 Smoke detectors 

must be installed in

the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power.  If
detectors are not so located, a developing fire may dam-
age the alarm system, crippling its ability to report a fire.

Audible warning devices

 such as bells may not alert

people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building.  Any warning device may fail to alert
people with a disability or those who have recently con-
sumed drugs, alcohol or medication.  Please note that:

Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.

Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal.  It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.

In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.

A fire alarm system

 will not operate without any

electrical power.  If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.

Equipment used in the system

 may not be technically

compatible with the control.  It is essential to use only
equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from

a premise to a central monitoring station may be out of
service or temporarily disabled.  For added protection
against telephone line failure, backup radio transmission
systems are recommended.

The most common cause

 of fire alarm malfunction is

inadequate maintenance.  To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards.  At a minimum, the
requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance.  A mainte-
nance agreement should be arranged through the local
manufacturer's representative.  Maintenance should be
scheduled monthly or as required by National and/or
local fire codes and should be performed by authorized
professional fire alarm installers only.  Adequate written
records of all inspections should be kept.

While a fire alarm system may lower insurance

rates, it is not a substitute for fire insurance!

Fire Alarm System Limitations

Содержание LDM-32F

Страница 1: ...Lamp Driver Module LDM 32F Instruction Manual Document 50055 03 20 2001 Rev C PN 50055 C0 ECN 01 155...

Страница 2: ...xplosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined...

Страница 3: ...pated or encountered Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing...

Страница 4: ...4 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...

Страница 5: ...witch 13 SW4 Alarm Trouble Mode Switch 13 Terminal Blocks 14 TB1 24 VDC Power Earth Ground and Supervision 14 TB2 EIA 485 In Out 14 Cables 14 Expander Ribbon Cable 14 The LDM CBL24 and LDM CBL48 14 Ke...

Страница 6: ...nd Testing the LDM 32F 33 Power Supply Connection 34 MPS 24AF Main Power Supply 34 MPS 24BF Main Power Supply 34 EIA 485 Connection 34 Lamp LED Driver Operation 35 Alarm Only Operation 37 Alarm Only O...

Страница 7: ...tion Diagram 49 Appendix C MS 9600 Capabilities 51 Trouble Indication 51 Programming and Testing the LDM 32F 51 Power and EIA 485 Connections 51 Configuration 52 Setting Rotary Switches 52 Alarm Only...

Страница 8: ...8 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...

Страница 9: ...of NAC outputs Alarm relay activation Other control functions The modules interface to the host fire alarm control panel via an EIA 485 communications bus circuit A maximum of 32 LDM 32Fs may be conn...

Страница 10: ...d troubles and other functions Switch SW4 is used to configure the module to annunciate 32 alarms or 16 troubles A green ON LINE LED flashes to indicate ongoing communications withthehostFACP OneLDM 3...

Страница 11: ...um of 56 alarm indicators 56 trouble indicators 16 status indicators and 64 optional controlswitch inputs Multiple sets ofLDM 32Fswith LDM E32F expanders increase the system annunciation capabilities...

Страница 12: ...ctor is provided as an input on LDM 32F and LDM E32F modules for an external security key switch Key switch contacts must be Normally Closed The keyswitchpreventsunauthorizeduse ofremote control switc...

Страница 13: ...system requiring annunciation of alarms and troubles for all 198 points would require four sets of LDMs with addresses 01 02 03 and 04 The MS 9600 is an exception refer to Appendix C MS 9600 on page 5...

Страница 14: ...IA 485communicationsbuscircuitforproperoperation The EIA 485 bus carries commands and data sent between the host FACP and the LDMs The input must be power limited Cables Expander Ribbon Cable The Expa...

Страница 15: ...ity A UL listed key lock switch wired to J4 on the LDM 32F should be used to provide access security for all control switches wired to that set of LDM modules Note Control switches will not function w...

Страница 16: ...1 Introduction Related Documentation 16 LDM 32F PN 50055 C 03 20 01 NOTES...

Страница 17: ...provided by custom graphic annunciator manufacturers may be used provided they meet UL requirements as UL listed secured enclosures CHS 4L Chassis The CHS 4L chassis will support one LDM 32F module a...

Страница 18: ...tional modules or expanders Figure 5 Installing LDM Modules in CHS 4L Connect an expander ribbon cable P N 75120 from the LDM 32F connector J2 to J3 of the first LDM E32F expander module If multiple L...

Страница 19: ...wire resistance to 10 ohms Connect the Grounding Cable from the chassis to the earth ground terminal of TB1 EARTH Connect 24 VDC power to the POWER IN and COMMON IN terminals of TB1 Figure 7 24 VDC Po...

Страница 20: ...dules used Communications between the Fire Alarm Control Panel and the LDM 32F is accomplishedoveratwo wireEIA 485serialcommunicationsbuswhichmust be power limited Communications between the host FACP...

Страница 21: ...ld in Conduit EIA 485 Shield Not in Conduit When the EIA 485 wiring is not in conduit terminate the shield at the outside of the FACP cabinet Do not allow the shield to enter or even touch the cabinet...

Страница 22: ...he EIA 485 Out terminals at the last LDM 32F on the circuit see below All other LDM 32Fs should not have a resistor installed Figure 12 EIA 485 Terminal Block TB2 Multiple wiring of EIA 485 circuits F...

Страница 23: ...lt output from LDM 32F J11 pin 1 Figure 14 Typical LDM to Graphics Display Connection 5VDC The figure below illustrates LEDs being powered by the 24 volt output from LDM 32F J9 pin 3 Figure 15 Typical...

Страница 24: ...must be key lock type secured in a locked enclosure or a security key switch must be installed to control access All switches must be installed in the same room as and no more than 20 feet from the L...

Страница 25: ...e arrow on SW2 tens so it points to 0 and position the arrow on SW1 ones so it points to 1 Figure 17 Address Switches SW1 SW2 Function DIP Switch SW3 These switches are used to determine how the LDM 3...

Страница 26: ...LDM series hold the same address all but one must be configured as Receive Only 6 Piezo Disable Set this switch ON to disable the piezo from sounding for any event The piezo will also be disabled if F...

Страница 27: ...t control panel Graphic Annunciator Lamps LEDs To adhere to standard fire alarm control panel convention and remain consistent with otherproducts that may exist in the system the following color conve...

Страница 28: ...3 Operation Graphic Annunciator Lamps LEDs 28 LDM 32F PN 50055 C 03 20 01 NOTES...

Страница 29: ...nd of the EIA 485 bus it willprovidesupervision ofReceiveOnly LDMs located on theEIA 485 bus between the Receive Transmit LDM and the FACP Receive Transmit LDM 32F LDMs that are configured to serve as...

Страница 30: ...4 LDM Communications Receive Transmit LDM 32F 30 LDM 32F PN 50055 C 03 20 01 NOTES...

Страница 31: ...larm and Trouble Display Mode and employing three expanders could have as many as 128 LEDs all of which are activated during Lamp Test Maximum Current per Driver 100 mA external circuit must limit cur...

Страница 32: ...n tables of the installation manual 2 EnterAlarmCurrentTotalobtainedhereintothealarmcalculationtables of the installation manual Table 3 Power Requirement Calculations Standby Current Number of LDM 32...

Страница 33: ...can 2000 Manual System Control Switches Acknowledge Signal Silence System Reset Activate selected system outputs notification circuits relays System Control Switches on the Sensiscan 2000 CPU may be r...

Страница 34: ...ore than 200 mA current can be drawn from these terminals in standby or alarm Figure 22 MPS 24BF Power Supply Connections EIA 485 Connection The EIA 485 bus that communicates with the LDM must be conn...

Страница 35: ...as shown above to points 57 through 64 provided those points exist in the system and the LDM 32F is set to address 01 Alarm Red LED Trouble Supv Yellow LED Control Switches2 2 Optional control switch...

Страница 36: ...Status per Circuit Trouble Status per Circuit Not Used IZ 4F IZE 4F Alarm Status per Circuit Trouble Status per Circuit Not Used IC 4F IC 4CCF Indicates Activation2 2 These Status LEDs are active only...

Страница 37: ...nts P57 through P64 dedicated to the Sensiscan 2000 system status annunciation see Figure 24 below Itisassumedthatthe 8 PointShift willbeselectedonlyonsystemscontaining 56 zones points or less or a to...

Страница 38: ...configuration of the LDM Series modules to annunciate alarms and troubles for up to 56 zones points with the last eight points 16 LEDs J7 P1 through P8 and J8 P1 through P8 dedicated to Sensiscan 2000...

Страница 39: ...4 Zones or Points Alarm Second 4 Zones or Points Trouble Second 4 Zones or Points Alarm Third 4 Zones or Points Trouble Third 4 Zones or Points Alarm Fourth 4 Zones or Points Trouble Fourth 4 Zones or...

Страница 40: ...32F and are assigned to Circuits 57 through 64 as shown below Note It is assumed that Sensiscan 2000 systems with 8 Point Shift selected will be 56 zones points or less Table 10 Switch Control Functio...

Страница 41: ...the panel s display Programming and Testing the LDM 32F After complete installation the Lamp Driver Module s must be programmed into the control panel as if it were an annunciator After programming t...

Страница 42: ...f address 01 dedicated to the MS 9200 system function LEDs see Figure 29 below Table 11 Alarm Only Setup Alarm Only Annunciation of Zones With 8 Point Shift The table below illustrates the configurati...

Страница 43: ...es to annunciate the alarm and trouble states for all 56 softwarezoneswiththelasteightpointsofaddress 01 dedicatedtotheMS 9200 system functions as listed below see Figure 32 on page 44 Table 14 Alarm...

Страница 44: ...18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 J5 J6 J7 J8 LCM32F conn cdr Alarm First 4 Zones or Points Trouble First 4 Zones or Points Alarm Second 4 Zones or Points Trouble Second 4 Zones or Points...

Страница 45: ...address 03 and 04 for modules Table 16 Alarm Only Setup Modules LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F Sys Funct 1 to 8 9 to 16 17 to 24 LDM E32F 25 to 32 33 to 40 41 to 48 4...

Страница 46: ...dules Set address 03 and 04 for modules Table 18 Alarm Only Setup Modules shift LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F 1 to 8 9 to 16 17 to 24 25 to 32 LDM E32F 33 to 40 41 to...

Страница 47: ...32F System Functions 1 to 4 5 to 8 1st LDM E32F 9 to 12 13 to 16 17 to 20 21 to 24 2nd LDM E32F 25 to 28 29 to 32 33 to 36 37 to 40 3rd LDM E32F 41 to 44 45 to 48 49 to 52 53 to 56 LDM Module Address...

Страница 48: ...5 J6 J7 J8 LDM 32F 1 to 4 5 to 8 9 to 12 13 to 16 1st LDM E32F 17 to 20 21 to 24 25 to 28 29 to 32 2nd LDM E32F 33 to 36 37 to 40 41 to 44 45 to 48 3rd LDM E32F 49 to 52 53 to 56 System Functions LDM...

Страница 49: ...2F addressed as 01 must be placed at the end of the EIA 485 circuit in order to provide electrical supervision of the wiring between all LDMs on the loop Figure 33 Configuration for 198 Point Alarm Tr...

Страница 50: ...Appendix B MS 9200 Configuration 50 LDM 32F PN 50055 C 03 20 01 NOTES...

Страница 51: ...EIA 485 bus is supervised by the MS 9600 Loss ofcommunication results in system trouble message on the panel s display Programming and Testing the LDM 32F After complete installation the Lamp Driver M...

Страница 52: ...s 1 56 2 0 2 Zones 57 99 2 NACs 3 0 3 Loop 1 Address M1 M64 4 0 4 Loop 2 Address M1 M64 5 0 5 Loop 1 Address M65 M128 6 0 6 Loop 2 Address M65 M128 7 0 7 Loop 1 Address M129 M159 Loop 2 Address M129 M...

Страница 53: ...9600 system functions see Figure 35 below Table 25 Alarm Only Setup with Shift Figure 35 System Functions to Output Connectors 1 LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F Sys Fu...

Страница 54: ...Setup with Shift LDM Module Address 01 LDM Output Connectors J5 J6 J7 J8 LDM 32F System Functions Z1 to Z4 Z5 to Z8 1st LDM E32F Z9 to Z12 Z13 to Z16 Z17 to Z20 Z21 to Z24 2nd LDM E32F Z25 to Z28 Z29...

Страница 55: ...conn cdr Alarm First 4 Zones or Points Trouble First 4 Zones or Points Alarm Second 4 Zones or Points Trouble Second 4 Zones or Points Alarm Third 4 Zones or Points Trouble Third 4 Zones or Points Al...

Страница 56: ...rol panel s SLC Loop 1 Modules M65 to M128 in Alarm Trouble mode See Figure 36 on page 55 By referring to Table 23 on page 52 it can be determined what address can be set to annunciate any other group...

Страница 57: ...39 44 55 56 alarms 10 37 alarms and troubles 38 annunciation capabilities 11 annunciator functions 13 annunciators 29 B battery 9 BCD switches 13 bipolar 12 31 C CAB A3F and CAB B3F 17 cabinet 21 cabi...

Страница 58: ...s 20 group of address points 56 I I O module 40 I O point 33 41 51 impedance 20 indicating device circuit 27 initiating circuits 33 initiating device circuit 27 intermediate display 29 J J1 32 J2 14 1...

Страница 59: ...32 programmed 33 41 42 51 R Receive Only 13 26 Receive Transmit 13 49 red 23 regulated 14 relay circuits 27 remote control switches 9 12 remote location 29 remote switch functions 10 removable termin...

Страница 60: ...51 time control circuits 27 track 35 transient protection 17 trouble 11 trouble condition 27 trouble drivers 24 trouble indication 12 trouble indicators 11 trouble points 23 trouble signal 14 20 trou...

Страница 61: ...LDM 32F PN 50055 C 03 20 01 61...

Страница 62: ...62 LDM 32F PN 50055 C 03 20 01...

Страница 63: ...ansportation prepaid to the manufacturer This writing constitutes the only warranty made by this manufacturer with respect to its products The manufacturer does not represent that its products will pr...

Страница 64: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com...

Отзывы: