IPDACT Module - Introduction

 

I-4

 

Doc.

Dm373-I 

Rev.

2.0

 

 

address  is  given  to  the  IPDACT  and  is  the  primary  communication  option.  
The backup 

VisorALARM

 IP address is also configured and is used in cases 

where  the  main  device  fails).    If  the  exchange  of  messages  does  not  occur 
during the configured time, the IPDACT tries to resend.  If, after a configurable 
number  of  attempts,  a  satisfactory  response  is  not  received,  the  connectivity 
with the main 

VisorALARM

 is presumed lost.  At this point the IPDACT tries 

to  communicate  with  the  backup 

VisorALARM

,  to  which  it  will  now  try  and 

send the alarms, polls, etc.  In cases  where communication  with this second 
device also fails, the telephone line access is returned to the control panel as 
if the IPDACT was not present.  From this point on, the IPDACT will try to re-
establish  communications  both  with  the  main  Teldat 

VisorALARM

  and  the 

backup,  communication  with  the  main  device  taking  priority.    The  moment 
communications  are  reestablished  with  either  of  the  two  ARC  devices,  the 
IPDACT intercepts the telephone line once more. 

The  supervision  traffic  is  encrypted  UDP.    The  Ethernet  frame  size  does  not 
exceed  70  bytes.    The  monitoring  interval,  the  number  of  retries  and  time 
between  retries  are  all  configurable,  and  are  values  that  must  be  carefully 
considered.    Normally  the  monitoring  interval  in  the  control  panel  is  high  as 
this  implies  a  telephone  call.    However,  in  the  case  of  IPDACT,  this  cost  is 
irrelevant as it is dealing with traffic which in all likeliness is running over a flat 
rate connection.  In addition, a high value here is not advisable in cases where 
the  IPDACT  connects  to  Internet  through  a  router  executing  NAT,  a  very 
probable situation.  This is because traffic coming from the ARC towards the 
IPDACT  reaches  this  thanks  to  the  router  maintaining  the  entry  in  the  NAT 
table active during a period of time, the entry being refreshed with supervision 
traffic.    If  the  supervision  interval  is  greater  than  the  residence  time  for  the 
entry  in  the  NAT  table,  communications  from  the  ARC  will  not  be  possible.  
There  is  no  rule  to  say  how  long  an  entry  in  the  NAT  table  must  last  for.    In 
cases of the TELDAT devices, this is around 5 minutes.  A low value has the 
problem  that  the  traffic  the 

VisorALARM

  must  process  is  high,  the  same  as 

the  bandwidth  requirements.    If  ARC  Internet  access  is  ADSL,  you  need  to 
consider  that  the  upstream  channel  is smaller than the  downstream one  and 
that  supervision  traffic  returned  to  the  IPDACTs  is  slighter  larger  than  the 
incoming. 

The incoming traffic to the ARC is: 

mips

ALIVE

KEEP

N

T

C

*

*

528

=

 

The minimum supervision time can be 1 second and a VisorALARM can have 
3000 IPDACTs registered that give an input traffic of 1,58 Mbps.  The return 
traffic is approximately 6% larger. 

The  Teldat 

VisorALARM

  received  monitoring  messages  from  the  IPDACTs.  

If  these  are  registered,  they  are  assumed  alive  and  an  acknowledgement 
response is sent to them; if the IPDACTs are not registered, they are ignored.  
Periodically the status of all the registered IPDACTs is checked and all those 
which have not notified their availability (i.e. those which have not responded 

Содержание IPDACT

Страница 1: ...IP Communicator IPDACT Installation Manual Document DM373 I Version 2 0 March 2007...

Страница 2: ...and cabling III 17 III 1 Installation III 17 III 1 1 Assembly Instructions for the IPDACT box III 19 III 2 Wiring III 20 III 2 1 Wiring for UL Listed Fire Installations III 20 III 2 1 1 Installation...

Страница 3: ...6 Monitoring IV 44 IV 5 Telnet IV 46 V Chapter Appendix V 47 V 1 UL Compliance V 47 V 2 Control Panels V 47 V 3 Technical Specifications V 48 The manufacturer reserves the right to introduce changes...

Страница 4: ...tional public switch telephone network and sends them through a serial port to automation software in order to be processed Additionally this receives monitoring messages from multiple IPDACT and gene...

Страница 5: ...on in the IP network Public Telephony Switched Network Alarm Control Panel Client hec ho p or M A B errojo Teldat C Intenet router router Eth 10 Mbps Eth 10 Mbps Alarm Receiver Sur Gard Radionics Viso...

Страница 6: ...onitoring procedures modified in order to contemplate the presence of two devices in the central I 1 2 1 Monitoring The IPDACT is a device that intercepts the control panel telephone connection with t...

Страница 7: ...h traffic which in all likeliness is running over a flat rate connection In addition a high value here is not advisable in cases where the IPDACT connects to Internet through a router executing NAT a...

Страница 8: ...r and lastly S is the frame validation digit When the panel opens to send an alarm the IPDACT provides power and emits the dialing tone When the control panel dials the alarm center telephone number i...

Страница 9: ...r multiple configuration parameters used by the IPDACTs Additionally in order to simplify the IP parameters configuration something that is not always easy the IPDACT has a DHCP client program release...

Страница 10: ...General Description The figure displayed below represents the IPDACT hardware Figure 4 IPDACT The hardware version and release is identified through its board number which is TS 540 X where X is the...

Страница 11: ...IPDACT Module Description II 8 Doc Dm373 I Rev 2 0 Figure 5 Board identification details The IPDACT basically consists of two elements the control module and the telephonic module...

Страница 12: ...manages the entire telephonic interface with the control panel and the client telephone network public telephone network termination point and client phone wiring From a configuration monitoring poin...

Страница 13: ...occurs when the IPDACT has connectivity with the configured VisorALARM The relays also activate when the telephone console activates please see section IV 2 for further information When the control p...

Страница 14: ...ch as a screwdriver or a clip This permits two tasks a On device startup this permits you to configure the IPDACT with the default configuration For further information on how to activate the default...

Страница 15: ...nals stop being short circuited Short circuit is carried out through an electric mechanical relay The technical data for this can be found in appendix V 3 OUT NO terminals whose state is normal open O...

Страница 16: ...ompliant GND power ground terminal II 5 LAN The device connects to the LAN through an RJ45 CN1 connector Figure 9 LAN Connector and cable Failure detection in the Ethernet interface is indicated by th...

Страница 17: ...Module Description II 14 Doc Dm373 I Rev 2 0 Figure 10 DB9 RJ45 converter for the console connection Figure 11 Console connector details The access configuration is 9600 8N1 8 bits without parity 1 st...

Страница 18: ...onment is a simple one orientated to menus The main menu is displayed in the following figure Main Menu Configuration a Generic MIP config b Remote Alarm report c Quick Install Monitoring d General In...

Страница 19: ......

Страница 20: ...es the telephone network to transmit alarms to an IP network The module can be connected to a wide variety of panels although only the panels given in the list in the appendix V 2 should be used for U...

Страница 21: ...IPDACT Module Installationg and cabling III 18 Doc Dm373 I Rev 2 0 Figure 13 Box with IPDACT The following diagram shows the IPDACT installation within the box...

Страница 22: ...control panel is 6 1 meters twenty feet 2 Remove screws 1 2 3 and 4 3 Place the IPDACT board so orifices A B C and D coincide with the bolts 4 Insert the four bolts into the orifices and slowly tighte...

Страница 23: ...er to reach the panel 9 The PSTN and PHONE telephone wires can also enter through the opening indicated in point 9 if the said cables come from the panel 10 The Ethernet cable can also enter through t...

Страница 24: ...ol Panel the following must be fulfilled The circuit connections extended to additional fire alarm control unit equipment when these wiring connections are intended to be made within 20 feet 6 1 m of...

Страница 25: ...re you have disconnected all power sources In these installations the IPDACT must be integrated in its box Connect the IPDACT box ground to the same ground point where you have connected the panel gro...

Страница 26: ...is to avoid electromagnetic interferences being conducted to inside the devices Figure 21 Ferrites for power cables The fire panel has two telephone lines in order to send alarm One is the main line...

Страница 27: ...elephone connection The following figure shows the connection between the IPDACT and the main telephone line in greater detail Figure 23 IPDACT Connection Main telephone line Do not connect any teleph...

Страница 28: ...given that the PSTN input is not operative there isn t a line Nor is there a telephone line to the panel s PRI PHONE LINE input This situation provokes an alarm in the panel which is then sent to the...

Страница 29: ......

Страница 30: ...gh a telnet session to the IPDACT IP address provided that the said IP address is available if this is in the same LAN for example In cases of a telnet session the given interface is identical to the...

Страница 31: ...ess assignment in the DHCP protocol is defined so that this can be permanent or expire after a certain period of time configurable in the DHCP server If the assignment is permanent the IPDACT will not...

Страница 32: ...re used to connect the IPDACT to the control panel consequently the telephonic console is not always available and it s necessary to activate it To activate the telephonic console short circuit the P1...

Страница 33: ...ll hear a simple beep indicating that this register can be configured From this point you can configure the first field in the register Should you select an invalid register an error signal is emitted...

Страница 34: ...s done as such to prevent errors when configuring the device and to reduce the time required for the process The passwords are verified through repetition The checking digit is obtained through the MI...

Страница 35: ...DHCP server is down The register is made up of 8 fields both the IP address as well as the mask is composed of 4 numbers between 0 and 255 Each number has a verification digit This contains the follo...

Страница 36: ...u to reset the IPDACT so that some parameters have validity So that the operation is effective you need to provide the access password for the console The register is made up of a single field corresp...

Страница 37: ...LIVE_INTERVAL Time interval when the IPDACT executes a connectivity test with the Teldat VisorALARM For this a keep alive frame is sent and a response is expected from the IP receiver The register is...

Страница 38: ...for this Default is Interval between backup keep alives seconds Time period where the IPDACT executes a check on connectivity with the backup Teldat VisorALARM To do this the IPDACT sends a keep aliv...

Страница 39: ...ceed in communicating with the backup after all the retries have been executed the telephone relays switch to allow the control panel to send the alarm over the telephone line The register is made up...

Страница 40: ...ing a programmable period of time open for a set time 2 seconds and returning to the closed state This behavior is maintained while there is no connectivity Switch time can take values between 0 and 3...

Страница 41: ...In order to increase the reliability of the telephonic console some registers require an additional testing digit in each of their fields so that if the control digit does not adjust to the introduced...

Страница 42: ...ll receive the configuration defined in the profile configured in the VisorALARM Through this mechanism the installed IPDACT is registered in the Teldat VisorALARM which from this point begins to moni...

Страница 43: ...orAlarm principal 12 010 024 006 001 IP VisorAlarm backup 21 080 036 189 123 UDP Port 13 03000 And in cases where the testing digit is enabled IP Address del IPDACT 01 1928 1684 0018 1008 2550 2550 25...

Страница 44: ...is the same as that configured in the telephonic console register 03 This is 24680 by default Entering the valid password accesses the main menu Password IV 4 2 Main Menu This provides access to the...

Страница 45: ...ents PHON g PC verifying digit 0 z Exit option IV 4 4 Monitoring configuration and sending of alarms Configures everything relative to the IPDACT as a security element Permits you to configure the acc...

Страница 46: ...hone len 3 m Tx retries 5 Output n Output Switching Period 20 PSTN Survaillance o Action due to Alarm BOTH z Exit option IV 4 5 IPDACT Quick Configuration This allows an installer to completely config...

Страница 47: ...d During the automatic register none message is dumped in the console The way to know the status of the automatic register is by checking the LED_A This LED is blinking while the IPDACT does not recei...

Страница 48: ...t are running in the device If the device has not obtained an address through DHCP this displays the IP address mask and gateway configured in the a Generic MIP config menu If on the other hand IP con...

Страница 49: ...e the telnet client indicating the IPDACT IP address The interface for this said console is identical to the one for the asynchronous console so for further information on this please see the section...

Страница 50: ...Control Units and Accessories for Fire Alarm Systems V 2 Control Panels The above standards are guaranteed with the following lists of panels Fire Panels MS 9200UD MS 9600 MS 9200UDLS MS 9600LS MS 905...

Страница 51: ...OPERATING TEMPERATURE 0 to 49 C 32 to 120 F RELATIVE HUMIDITY Maximum 93 LAN Port CONNECTOR RJ45 female SPEED 10 Mbps PROTOCOLS UDP IP ARP DHCP Telnet Ethernet Blue Book Other Characteristics OUTPUT...

Отзывы: