background image

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code,
applicable local codes and the Authority Having Jurisdiction. Proper wire
gauges should be used. The installation wires should be color coded to limit
wiring mistakes and ease system troubleshooting. Improper connections will
prevent a system from responding properly in the event of a fire.

Remove power from the communication line before installing sensors.  

1. Wire the sensor base (supplied separately) per the wiring diagram, 

see Figure 1.

2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base.  Push the sensor into the base while turning it clockwise to secure it in place.  
4. After all sensors have been installed, apply power to the control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.

TAMPER RESISTANCE
The sensor base includes a tamper proof feature which when activated prevents
removal of the sensor without the use of a tool. See the installation instruction
manual for the sensor base for details in using this feature.

TESTING SENSITIVITY

Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of
service. Disable the system to prevent unwanted alarms.  

All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having
Jurisdiction (AHJ).  Sensors offer maximum performance when tested and maintained in compliance with NFPA 72.

A. Test Magnet (p/n M02-04-01 or M02-09-00)

1. Place the optional test magnet against the cover in the magnet test area, as shown in Figure 3, to activate the test

feature.

2. The LEDs should latch on within 10 seconds, indicating alarm and annunciating the panel.
3. Reset the detector at the system control panel.

F300-25-00

2

I56-1972-00R

LISTED COMP

A

TIBLE

CONTROL

P

A

NEL

Figure 2

TENS

Breakaway Stop

ONES

9

10

11
12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

Figure 1

CAUTION:

Do not loop wire under terminals 1 or 2.
Break wire run to provide supervision of connections.

A78-2745-00

Содержание H355

Страница 1: ... temperature alarm Model H355R is a rate of rise temperature sensor with 135 F fixed temperature alarm Model H355HT is a high temperature sensor with 190 F fixed temperature alarm Two LEDs on each sensor light to provide a local visible sensor indication Remote LED annunciator capability is avail able as an optional accessory Part No RA400Z Models H355 H355R and H355HT require compatible addressab...

Страница 2: ...ch when activated prevents removal of the sensor without the use of a tool See the installation instruction manual for the sensor base for details in using this feature TESTING SENSITIVITY Before testing notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service Disable the system to prevent unwanted alarms All sensors must be tested after instal...

Страница 3: ...s described under MAINTENANCE and retested If the detectors still fail these tests they should be returned for repair Figure 3 Views showing position of test magnet F300 25 00 3 I56 1972 00R LED TEST MAGNET MARKER LED TEST MAGNET MARKER A78 1478 06 A78 1944 02 MAINTENANCE NOTE Before cleaning notify the proper authorities that the system is undergoing maintenance and therefore the system will temp...

Страница 4: ...iate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harm ful interference to radio or television reception which can be determined by turning the equipment off and on the user is enc...

Отзывы: