411UD Document #50759 Rev. E 12/09/2008 P/N 50759:E
35
Program Mode
Backup Reporting (61)
Leaving address 61 at '0' means that reports will be transmitted to the secondary Central Station phone number
only if attempts to communicate to the primary Central Station phone number are unsuccessful. Programming a
'1' causes all reports to be transmitted to both the primary and secondary Central Station phone numbers. Pro-
gramming a '2' causes reports to go to the first available receiver.
CAUTION: Do not alter this entry while the digital communicator is active.
Reserved for Future Use (62)
Reserved for Future Use (63)
Communicator Enable/Disable (64)
Leaving address 64 at the factory default setting of '0' prevents the digital communicator from transmitting status
information to the Central Station(s). An entry of '1' in this location enables communication to the Central
Station(s).
Note that upon power-up, the 411UD will immediately annunciate a DACT trouble since the communicator is fac-
tory defaulted to 'communicator disabled' at program location 64.
Input Channel Function Selections - When selecting Input Channel functions, be certain to match the host panel
relay output functions with the Input Channel functions. Test all wiring connections completely. All Input Channels
require Normally Open contact closure to trigger. Input Channels do not latch.
Input Channel 1 Function Selection (65)
1
Factory default for Channel 1 is '0' for activation on Fire Alarm. Enter '1' for Host Control Panel Trouble; '2' for
Fire Supervisory; '4' for AC Loss.
Input Channel 2 Function Selection (66)
1
Factory default for Channel 2 is '1' for activation on Host Control Panel Trouble. Enter '0' for Fire Alarm; '2' for
Fire Supervisory; '4' for AC Loss.
Input Channel 3 Function Selection (67)
1
Factory default for Channel 3 is '2' for activation on Fire Supervisory. Enter '0' for Fire Alarm; '1' for Host Control
Panel Trouble; '4' for AC Loss.
Input Channel 4 Function Selection (68)
1
Factory default for Channel 4 is '4' for activation on AC Loss. Enter '0' for Fire Alarm; '1' for Host Control Panel
Trouble; '2' for Fire Supervisory. Note that the AC Loss function requires a Normally Open contact dedicated to
AC loss function. The 411UD transmits a specific AC Loss event code if desired.
1. Changing the input function will automatically change the corresponding Primary and Secondary event codes to reflect the new
input function. The Communication Format should be programmed first, followed by the Input Channel Function.
!