Program Mode
To exit Real Time Clock Mode before completing clock programming, press the
MODE
key, followed by the 4-digit
code for an alternate mode and then the
[ENTER/STORE]
key. During Real Time Clock Mode, if no key is pressed
within 10 minutes, the communicator will revert to Normal Mode.
Note that upon power-up, the internal clock starts running at 00:00 midnight. It must be changed so that the 411UD
can accurately call in test signals to the Central Station. Upon power loss, the clock reverts to 00:00 midnight and
must be reset.
3.3
Program Mode
All programming selections made during Program Mode are stored in nonvolatile Electrically-Erasable Programma-
ble Read-Only Memory (EEPROM). This ensures that the 411UD will retain all entries made in Programming Mode
even if power is removed.
The user must program the primary and secondary phone numbers, account numbers, 24-hour test report times and
verify event codes for each Central Station account. The 411UD is shipped with the program options/features already
factory programmed. Alternative options/features may be programmed if desired. If all factory default settings are
acceptable, programming is complete.
Program Mode is entered by pressing the
MODE
key followed by the 4-digit program mode entry code
7764
and
pressing the
[ENTER/STORE]
key.
7764
spells PROG on a Touch-Tone
®
phone.
If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE]
key. Note that as
information is entered into the 411UD, the digits will scroll across the Programmer display from right to left.
___7
__77
_776
7764
A pause of up to 10 seconds between each number is allowed while entering the code. After pressing the
[ENTER/
STORE]
key, the digital communicator will be in Program Mode. A maximum of 10 minutes idle time is allowed at
this point before beginning program entries and between each key stroke, otherwise, the digital communicator will
return to Normal Mode. All entries made prior to the 10 minute time-out are valid and are stored.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must
be limited to specific values or not used at all as indicated below:
Program feature
or option
Permitted in
UL 864? (Y/N)
Possible settings
Settings permitted
in UL 864
Trouble Call Limit
N
Program Address 89 = 0 (factory default): unlimited
calling to Central Station for any trouble condition
Program Address 89 = 1: limits call for each unique
trouble to 10 within a 24 hour period
Program Address 89
= 0 for unlimited
Central Station
trouble calls