ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
63
Master Programming Level
Programming
Pre-signal
To enable the Pre-signal feature, press
1
while viewing Edit Monitor Screen #3 until the display reads
Pre-
signal Yes
. Each press of the
1
key will cause the display to toggle between
Pre-signal Yes
and
Pre-signal
No
. Refer to“Presignal” on page 112 for additional information.
Wireless
The Wireless selection will update automatically if the system recognizes a wireless device. If the module is wireless, the display reads
Wireless Yes
. If the module is wired, the display will read
Wireless No
. Fore more information on the SWIFT wireless network,
refer to
the SWIFT manual
, #LS10036-000FL-E.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually reset-
ting the control panel after each device activation. To enable devices, which are connected to a monitor
module, for the Walktest feature, press
1
while viewing the Edit Monitor Screen #4 until the display reads
Walktest Yes
. Each press of the
1
key will cause the display to toggle between
Walktest Yes
and
Walktest No
.
Refer to “Walktest” on page 114 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing
2
while viewing Edit Monitor Screen #4
displays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first
0
to the left. Enter the three digit number corresponding to the zone that is
to be assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones
can be left blank or programmed as general alarm zones Z000. When all desired changes have been made, press the Enter key to store the
zone assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module
currently being programmed. Pressing
1
while viewing Edit Monitor Screen #5 will cause the following
screen to be displayed:
Ack Switch
Acts like panel Acknowledge Key
Sil Switch
Acts like panel Silence Key
Reset Switch
Acts like panel Reset Key
Drill Switch
Acts like panel Drill Key
PAS Bypass
PAS Disable
Switch (see note 2)
Acts like panel Drill Key, nonlatching (tracking)
Wireless Gateway
SWIFT gateway needs this type to display wireless troubles at the FACP
1
Combination systems employing these non-fire monitor types require the SLC loop to be
programmed by the installer for Class B operation and isolator modules must be employed on each
non-fire branch of the SLC as shown in the SLC Wiring Manual (document number 51309). Fire and
non-fire devices must not be used on the same SLC branch. For UL2017 compliance, The ANN-LED
annunciator must be used to indicate the active, dedicated zone or device
2
For entries ending in AR, AR refers to AutoResettable.
3
For HVAC RESTART and HVAC OVRRIDE descriptions, refer to “Monitor Module Operation” on
Table 3.1 Monitor Types
EDIT MONITOR
1=PRE-SIGNAL NO
WIRELESS NO
Edit Monitor Screen #3
EDIT MONITOR
1=WALKTEST YES
2=ZONE ASSIGNMENT
000
Edit Monitor Screen #4
ZONE ASSIGNMENT
Z000
Zone Assignment Screen
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Monitor Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
Содержание ES-200X
Страница 137: ...ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 137 Notes ...
Страница 164: ...164 ES 200X Series Manual P N LS10131 000FL E C 7 25 2018 ...
Страница 166: ...Cut along dotted line ...
Страница 168: ...One Fire Lite Place Northford CT 06472 1601 USA USA Phone 203 484 7161 Canada Phone 905 856 8733 www firelite com ...