ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
109
CO Alarm Operation
Operating Instructions
•
Third line in display:
Z000
indicates the zone programmed to this device which, in this example, is general alarm Zone 000. Note
that a single device can be programmed to five different zones but only the first zone will be displayed.
•
Fourth line in display:
Time; the current time in this example is
10:00A
which represents 10:00 AM
Date; the current month, day and year in this example is
01
for January,
08
for the 8th day of the month and
16
for the year 2016
Device Address;
1M001
in this example
1
represents SLC Loop,
M
represents a module and
001
represents device address 001
4.6 CO Alarm Operation
When a CO alarm operation occurs:
•
The piezo sounder produces a steady Temporal 4 output
•
The CO Alarm LED flashes 1 second On and 1 second Off
•
The LCD displays
CO Alarm
along with the device name, type, address, adjective/noun, associated zones and time/date
•
Communicate the CO alarm to the Central Station
•
CO alarms latch and
are not allowed to clear automatically
•
CO alarms activate software zones if so programmed
•
Timers for Silence Inhibit, Autosilence, and Alarm Reminder are started
•
CO alarms activate the relays programmed for CO alarm
•
The trouble relay is not activated
•
Store event in history buffer
•
Terminate upload or download communications
•
CO alarms must be Acknowledged before the FACP can be reset
A typical CO alarm display would be as illustrated below:
The information displayed in the above example provides the following information:
•
First line in display:
The type of event; in this example
ALARM
indicating a CO alarm condition
Device type identifier; in this example,
CAR MONOXIDE
indicates a CO detector.
•
Second line in display:
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC.
•
Third line in display:
Z002
indicates the zone programmed to this device which, in this example, is general alarm Zone 002. Note
that a single device can be programmed to five different zones but only the first zone will be displayed.
•
Fourth line in display:
Time; the current time in this example is
10:00A
which represents 10:00 AM
Date; the current month, day and year in this example is
09
for September,
08
for the 8th day of the month and
16
for the year
2016
Device Address;
1M001
in this example
1
represents SLC Loop,
M
represents a module and
001
represents device address 001
4.7 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
•
The piezo sounder pulses ½ second On and ½ second Off
•
The Supervisory LED flashes ½ second On and ½ second Off
•
The LCD displays the status label
Active Supervisory
along with the device name, type, address, adjective/noun, associated zones,
and time/date
•
Communicate the supervisory condition to the Central Station
•
The supervisory relay is activated
•
The alarm relay is not activated
•
Silenced alarms are resounded
•
Timers are not started
•
Store event in history buffer
•
Terminate upload or download communications
NOTE:
When using carbon monoxide detection the system must be monitored by a Supervising Station, meeting the Standard for the
Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.
ALARM CAR MONOXIDE
<ADJ> <NOUN>
Z002
10:00A 090816 1M001