L38DF-ST See-thru Gas Fireplace
Part No. XG0810
f i r e f e a t u r e
Installation
Figure 9.
Horizontal flex installation with MIN vertical rise.
B. Vertical (Through-The-Roof) Installations
Vertical rise >12' can be reduced (on applicable models).
Vertical Terminations must be installed:
•
minimum 2' (two feet) above the highest point where
vent passes through the roof.
•
minimum 6' (six feet) from a mechanical air inlet
•
minimum 18" (1 1/2 feet) from a parapet wall.
Figure 10.
Straight, vertical venting
showing required PXT-10 adaptor
(supplied with the PVTK-1 termination).
*
For venting MIN 1" clearance to all vertical combustibles,
MIN 2" to all horizontal combustibles.
RHS8
5" / 8" Venting
A - Termination
PVTK-1
B - Flex Sections
PFL-1 (12" Section)
PFL-2 (24" Section)
PFL-3 (36" Section)
PFL-4 (48" Section)
C - Rigid Sections PEXT-1 (12" m/f Section)
PEXT-2 (24" m/f Section)
PEXT-3 (36" m/f Section)
PEXT-4 (48" m/f Section)
D - Support Ring
& Plate
PSPXT-8
E - Firestop
PS-8
F - Roof Flashing PRF-7 (1/12 - 7/12 pt.)
PRF-7 (7/12 - 12/12 pt.)
G - Adaptor / Vent
Reducer
PVA5487 (5"/8" to 4"/7")
Maximum vent height is: 32 feet above fireplace.
Note: Flame characteristics will change if the maximum vent height
is used.
Minimum clearances 2" from vent to all combustible materials must
be maintained.
A maximum of two offsets
(each offset has two 90° bends)
may be
made and shall not exceed total length of 25% of the vertical vent
height, when measured center to center of piping.
Example:
Typical vent installation.
20' vertical vent
2 - 2' offsets required
25% of 20' = 5' max. offset allowed
This venting configuration meets requirements.
PEXT