Fire feature L38DF-ST Скачать руководство пользователя страница 10

Page 10

L38DF-ST See-thru Gas Fireplace

Part No. XG0810

f i r e   f e a t u r e

Figure 17b.

 Vertical venting with 2 offsets (1 offset= two 90° bends).

Figure 17a

. Vertical venting with 1 offset (1 offset= two 90° bends).

Installation

Vertical Vent Installations

 

Vertical Installations with a rise greater than 12' can be reduced 
from 5/8 to 4/7 venting.

 

 

minimum 2' (two feet) above the highest point where

   

vent passes through the roof.

 

 

minimum 6' (six feet) from a mechanical air inlet

 

 

minimum 18" (1 1/2 feet) from a parapet wall.

  Maximum vent height is 30 feet above fireplace.

  Note: Flame characteristics will change if the maximum vent 

height is used.

 

Minimum 

clearance to combustible construction around 

the vent pipe is 1"

 on all sides must be maintained, except on 

horizontal venting where the 

top

 of the pipe must have a clear-

ance of at least 2".

2. offset Vertical Installations

 

A maximum oftwo offsets

 (each offset has two 90° bends)

 may 

be made if the length of the offsets does not exceed 25% of the 
vertical vent height, when measured center to center of piping.

  Example: 

Typical vent installation.

   

 

30' vertical vent

   

 

2 - 2' offsets required

   

 

25% of 30' = 7-1/2' max. offset allowed

  This venting configuration meets requirements.

1. Straight Vertical Installation

Figure 17

. Straight, vertical venting. 

PEXT
Solid Sectio

n

PEXT

 Solid

Section

Содержание L38DF-ST

Страница 1: ...s supplier s instructions If you cannot reach your gas supplier call the fire department For Your Safety Do not store or use gasolineorotherflammable vapors and liquids in the vicinity of this or any...

Страница 2: ...ted in this manual Consult your local Gas Inspection Branch on installation requirements for factory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in...

Страница 3: ...e clearances apply to all dimensions except the framed opening where the clearance to combustibles is 0 The L38DF ST clearance to unprotected combustible walls which are perpendicular to the fireplace...

Страница 4: ...by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Vent Installation This section cove...

Страница 5: ...s in the termination MSR PTO 3F 5 8 PTO 3F 5 8 PTO 3F 5 8 PTKOG 5 8 1 Ensure that the two long mounting brackets are facing the bottom ofthetermination Seeinset Thiswillprovidemoreheatprotection at th...

Страница 6: ...Venting runs must fall within the limits set by the venting graph see Figure 9a Figure 8 Retracted Installation using a combination of solid and flex venting Use the vent graph to determine your allow...

Страница 7: ...ination PVTK 1 B Flex Sections PFL 1 12 Section PFL 2 24 Section PFL 3 36 Section PFL 4 48 Section C Rigid Sections PEXT 1 12 m f Section PEXT 2 24 m f Section PEXT 3 36 m f Section PEXT 4 48 m f Sect...

Страница 8: ...ll flange of the vent termination is 156 this would be an acceptable installation Example B Acceptable Installation If the vertical dimension from the hearth is 72 and the horizontal run to the wall f...

Страница 9: ...onents using the chart on Page 8 Figure 16 Extended horizontal installation using a combination of rigid and flex venting Figure 15 Heat Shield for short horizontal installation Install by slid ing ov...

Страница 10: ...ace Note Flame characteristics will change if the maximum vent height is used Minimum clearance to combustible construction around the vent pipe is 1 on all sides must be maintained except on horizont...

Страница 11: ...fireplace with a non combustible material Please Note The decorative facing materials may be subject to temperatures in excess of 250 F This should be considered when selecting facing materials We rec...

Страница 12: ...oors Both Sides Typical Cautions DO NOT OPERATE THIS FIREPLACE WITHOUT THE GLASS DOOR OR WITH A BROKEN GLASS DOOR p Cautions 5 1 60 Supply G L1 L2 NOTE If any of the original wire supplied with the ap...

Страница 13: ...Off Gas To Appliance Operation Model L38DF ST 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1...

Страница 14: ...not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructio...

Страница 15: ...ing Instructions To Turn Off Gas To Appliance 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 If the switch on the control module is set to Continuous Pilot Off th...

Страница 16: ...o inspect the appliance and to replace any part of the control system and any gas control which has been under water p p p p p Operation Lighting Instructions See pages 13 to 15 Burner Adjustment The...

Страница 17: ...s appear until the bubbling stops completely Figure 34 Pilot Burner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pil...

Страница 18: ...subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will prod...

Страница 19: ...feet minimum in the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum f...

Страница 20: ...rade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS...

Страница 21: ...Part No XG0810 f i r e f e a t u r e Maintenance Notes Spare Parts L38DF ST L DF ST NG Gas Valve RGC1006 LP Gas Valve RGC1005 NG Pilot RPA020 LP Pilot RPA021 Burner NG RBL38501 Burner LPG RBL38502 ROR...

Страница 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0810 041808 f i r e f e a t u r e...

Отзывы: