Correction formula for K-Factor calculation according to real internal
diameter:
K-Factor_NEW = (K-Factor x ID²) / ID_NEW²
ID = Value in the table for the internal diameter (in mm)
ID_NEW = New value for the real internal diameter (always in mm)
K-Factor = Value in the table
K-Factor_NEW = New K-Factor value for the specified internal diameter
Example:
Nominal Pipe Size (DN) = 100 mm
New Internal Diameter = 104 mm
Forumla: K-Factor_NEW = (51.02 x 100²) / 104² = 20,52
ORDERING DATA
Part No.
Version
Power
supply
Length Main wetted
materials
Enclosure
Flow Rate
Range
Weight
(gr.)
F3.00.W.13
Hall
See electrical
data section
L0
CPVC/EPDM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
750
F3.00.W.14
Hall
See electrical
data section
L0
CPVC/FPM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
750
F3.00.W.15
Hall
See electrical
data section
L1
CPVC/EPDM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
800
F3.00.W.16
Hall
See electrical
data section
L1
CPVC/FPM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
800
F3.00.W.17
Hall
See electrical
data section
L0
PVDF/EPDM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
750
F3.00.W.18
Hall
See electrical
data section
L0
PVDF/FPM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
750
F3.00.W.19
Hall
See electrical
data section
L1
PVDF/EPDM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
800
F3.00.W.20
Hall
See electrical
data section
L1
PVDF/FPM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
800
F3.00.W.21
Hall
See electrical
data section
L0
316SS/EPDM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
950
F3.00.W.22
Hall
See electrical
data section
L0
316SS/FPM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
950
F3.00.W.23
Hall
See electrical
data section
L1
316SS/EPDM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
1000
F3.00.W.24
Hall
See electrical
data section
L1
316SS/FPM
IP65
0.15 to 8 m/s
(0.5 to 25 ft./s.)
1000