SET PLUS 2.0 - SET 2.0
Annex 2:
SET PLUS 2.0 LFWC - 25/35/40 wiring diagram
CA
NC
AN
VF
S2
VFS1
S6
+
V2
V1
S5
S4
S3
S2
S1
-
R3
R3I
R2
R1
LN
PE
LV
UPM3 HYBRID PUMP
CONFIGURA
TION::
Press
➲
once to verify the pump configuration (
).
If the configuration does not match, press
➲
again and hold it pressed down for more than 2 seconds.
Press
➲
several
times
until
the
LED
bar
for
PWM
configuration
at
maximum
curve
illu
minates
(
).
W
ait 10 seconds.
The LEDs stop blinking and the new configuration is stored in me
mory
.
If
the
pump
configuration
is
correct,
the
pump
shall
be
in
the
stand-by
mode
and
the
first
LED
shall
be
green and blinking (
).
TERMINAL
BOARD WIRING DIAGRAM
230 V
AC
line side
Probe side max. 12 V
Danger
W
arning
SOREL
CONTROLLER
PUMP
-->
LFWC
Phase
-->
L
Neutral
-->
N
Ground
-->
*PEL
V
PWM V1
-->
Brown
-
-->
Blue
black wire NC and insulated
Power supply Phase
-->
L
Neutral
-->
N
Ground
-->
*PEL
V
SPECIAL
CONTROLLER FUNCTIONS
TO ENABLE:
6.1.1
Type of pump = PWM
6.1.2 Pump = Heating 6.1.3 Output signal = reversed
Flow meter VFS1 connector
230V
AC 50-60Hz power lines
Use right side of terminal board for connection
!
Terminal
:
Connection for
:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Relay 1
R2
Relay 2
R3
Relay 3 (normally closed)
R3I
Relay 3 (normally open)
The PE protective conductor shall be connected to the PE metal terminal board!
Lowe voltage
max. 12V
AC/DC
Use left side of terminal board for connection
!
Terminal:
Connection for
:
S1
Circulation (opt.)
S2
Cold water (opt. see below)
S3
Primary circuit (opt.)
S4
High storage (opt.)
S5
Medium storage (opt.)
V1
0-10V/PWM primary pump
signal
V2
0-10V/PWM signal (opt.)
S6
Primary circuit return (opt.)
-
Probe bridge
VFS1
Cold water inlet
VFS2
optional
The polarity of probes PT1000 can be selected freely
.
Relay connections change based on the additional functions selected. Connect grounding probe (1-6) with probe attached to terminal board (-). VFS probes shall be connected to the power outlet on the control panel. Probe 2 / Cold water: when not connected, no probe is set to a temperature of 10°C.