8 Wiring Instruction 

8.1 Preparations 

8.1.1 Please note the following safety precautions before use:

 

The instrument wiring is only permitted when it is powered OFF.   
If overvoltage occurs to the wire, please install overvoltage protection device to protect the 
instrument. 

 

8.1.2 Connecting cable

 

The instrument can be connected with the general 2-core wire without the shielding layer 
available on the market.   
If electromagnetic coupling phenomenon occurs to the installation and wiring environment, and 
the value exceeds the inspection value of EN61326-1 Standards applicable to the industrial 
field, the cable with shielding cable should be used. For the instrument with housing and cable 
screw thread connector, please use the cable with circular cross-section. Please check the 
external diameter of the cable applicable to the cable screw thread connector, so as to ensure 
the sealing on the cable screw thread connector (IP protection method). Please use the cable 
screw thread connector matching with the cable diameter.   
 

Note!   

When wiring, please follow the requirements of DIN EN 61140 VDE 0140-1(Protection against 
electric shock - Common aspects for installation and equipment), to guarantee the safety 
isolation between the power circuit and the grid circuit.   
When the cable with shielding isolated mesh is used, it is recommended setting up the 
shielding isolated mesh on both sides of earth potential. In the sensor, the shielding isolated 
mesh must be directly connected with the internal grounding terminal. The external grounding 
terminal on the housing must be connected with the low impedance of the earth potential. For 
explosion-proof equipment, it should perform grounding based on the requirements on the 
license.   
For the electroplating and KKS equipment (cathodic anticorrosion protection), the great 

potential difference should be considered. When the shielding isolated mesh is grounded on 

both sides, it may cause the current of the shielding isolated mesh to exceed the permitted 

scope.   

 

 

8.1.3 Power supply

 

The product is connected with a 2-core wire to supply power and send current signal   
Working voltage (Vs):   
With display adjustment module: 16~30VDC 
Load impedance:(Vs-Vmin)/0.022A 
For example: When supplying 24VDC for the instrument with display adjustment module: 
(24-16)/0.022 = 363

Ω 

 

Содержание JTR

Страница 1: ...l Sensor Operation Instruction FineTek Co Ltd No 16 Tzuchiang St Tucheng Industrial Park New Taipei City 23678 Tel 886 2 22696789 Fax 886 2 22686682 Website http www fine tek com E mail info fine tek...

Страница 2: ...eatures 10 6 Specification 11 7 Installation 15 7 1 General Instructions 15 7 1 1 Lock instrument 15 7 1 2 Moisture proof instructions 15 7 1 3 Operating conditions 15 7 2 Installation Instruction 16...

Страница 3: ...9 2 2 Display settings Menu 27 9 2 3 Diagnostics 29 9 2 4 Additional Settings Menu 30 9 2 5 Product Information Menu 31 9 3 Parameter table list 32 9 4 Bottom Tracking Probe Set up 34 10 Warnings and...

Страница 4: ...ll be uploaded onto our company website at www fine tek com users may download the information from there Please do not disassemble or repair the product yourself otherwise the warranty will become in...

Страница 5: ...to items that are used and installed accordingly It does not cover items that are used extraordinarily or outside its scope of operations The following conditions will result in product not be covere...

Страница 6: ...ffice Taiwan 886 7 333 6968 886 7 536 8758 Fine automation Co Ltd China No 451 Duhui Road Zhuanqiao Township Minhang District Shanghai City 201109 86 021 64907260 86 021 6490 7276 Aplus FineTek Sensor...

Страница 7: ...asurement accuracy Optional 3 2 Safety Check Before unpacking please check the package first for any damages or deformities If yes take photos for evidence After unpacking please check if the products...

Страница 8: ...ith a bottom tracking probe technology This function is very useful in increasing the sensitivity when the dielectric constant of the measured object is low such as the plastic particles material frag...

Страница 9: ...arger than 1 6 The media must be stable without change or mixture Moreover it must be uniform The minimum thickness of the media in L2 should be larger than 50mm 1 97 inch and L2 must be clearly separ...

Страница 10: ...he effects from steam foam and stirring 2 wire loop power for simple wiring Local LCM display for convenient on site adjustment Unique algorithm and echo processing technology can be applied in variou...

Страница 11: ...is greater Analog output 4 20 mA Power supply 16 30 Vdc Loop Power 16 30 Vdc 4 wire 5 10Vdc RS485 4 Wire Digital communication HART 7 3 for 2 Wire RS485 Modbus for 4 Wire Housing material Aluminum all...

Страница 12: ...gh 2 core wire via terminal block J2 Analog Out 2 I2 I2 Uo 13 65 V Io 69mA Po 0 236W Co 0 79 F Lo 7468 H Through 2 core wire via terminal block J3 JTR30XE 4 Wire 16 30Vdc 4 20mA with RS485 by 2 core w...

Страница 13: ...lent parameter Ci F Li mH D D 12 100 0 3 0 0 Max Voltage Output Uo V Max Current Output Io mA Max Power Output Po mW Max External Parameter Co F Lo mH 7 15 25 See below Terminal Code AO Max Voltage In...

Страница 14: ...enzene styrene toluene furan naphthalene 14m 6m 6m 4 0 7 0 chlorobenzene chloroform cellulose spray isocyanate aniline 16m 6m 6m 7 0 aqueous solutions alcohols ammonia 20m 6m 6m JTR302 Dielectric cons...

Страница 15: ...ure from entering the housing along the cable Please pay special attention to moisture proofing when the product is applied in the following environments Outdoor installation Installation in areas wit...

Страница 16: ...measure the lowest point of the sensor Note When welding is required for the installation please remove the electronic module of the sensor from the junction box before welding It can prevent the dam...

Страница 17: ...use extension pipe on the container Kindly install the sensor and the container cap flush with the ground When welding the connector of the extension pipe please make the edge of the extension pipe co...

Страница 18: ...position with liquid flow It can t provide accurate measurement when the liquid flows in 7 2 3 Blind area The measuring range is from the bottom of flange or hread Note t he measuring range is from t...

Страница 19: ...se follow the requirements of DIN EN 61140 VDE 0140 1 Protection against electric shock Common aspects for installation and equipment to guarantee the safety isolation between the power circuit and th...

Страница 20: ...insert it inside the housing 6 Connect the wire to the terminal according to the wiring diagram 7 Pull it gently to check whether the wire is fixed firmly on the terminal 8 Connect the shielding with...

Страница 21: ...21 4 wire type JTR30XH series JTR30XE series JTR30XF series The example for working with safety barrier Digital Signal JTR30XE TXX200...

Страница 22: ...ructions After the instrument is connected with the power supply and powered ON again it will start system initialization and self diagnosis for about 30 seconds Internal inspection of the electronic...

Страница 23: ...e electronic part at the required direction rotate clockwisely to fix it 3 Fasten the housing cover The disassembly should follow the reverse direction ENT button Enter the menu Confirm the selected c...

Страница 24: ...h can be set to probe length current percent When a single media is measured the two data values are corresponding to the same measurement value When it is applied in the liquid interface the upper pa...

Страница 25: ...Set 1 6 It is to set the current output direction 4 20mA 20 4mA Setting 1 1 Unit Type Application Probe Length Adjustment L V Unit Type m mm cm 1 1 1 in In the Unit 1 1 menu user may adjust the unit...

Страница 26: ...vent and Oil 3 Chemical Mixture 3 10 Aqueous Media 10 Setting 1 4 Unit Type Diagnostics Display Additional Set Adjustment L V 1 4 1 Min Adjustment Offset Adjustment Max Adjustment Offset Adjustment 1s...

Страница 27: ...Wherein the 2nd current set is only available for the models with dual analog output In this setting the user may set the current output to correspond to the distance or the material height with an ou...

Страница 28: ...ontent shown on the lower part includes Distance Percentage Current Display 2 3 Language Indication 1st Indication 2nd Lcd Contrast Indication 2nd Distance Height Percent Filling Height 2 3 1 Distance...

Страница 29: ...ance 3 1 1 MAX 597 mm MIN 581 mm Return Clear Peak distance 3 1 menu records the measured peak value after startup which can be queried and reset in this menu Echo Curve 3 2 menu shows the echo curve...

Страница 30: ...T Address HART Variables HART variable PV Distance HART variable SV Distance Percent HART Address 01 0 16 HART Mode 4 1 1 menu the first layer is divided into HART Variable and HART Address HART Varia...

Страница 31: ...model of the instrument Information 5 2 Product Model Serial Number Production Date Product Version Serial Number 5 2 1 JTR Txxxxxxx Serial No 5 2 menu allows you to view the product serial number of...

Страница 32: ...32 9 3 Parameter table list...

Страница 33: ...33...

Страница 34: ...lect for example like Metal Vessel and push ENT to save When selecting Liquids in Menu 1 3 1 following to push for related options like Vessel and push ENT to save Step 1 Selecting the Type of Medium...

Страница 35: ...saveWhen selecting Liquids in Menu 1 3 1 following to push for related options like Oil 3 and push ENT to save Step4 Calibration of D C dielectric constant Menu 4 2 2 use and to key in information fo...

Страница 36: ...Process temperature C T4 40 60 40 130 T3 40 60 40 190 T2 40 60 40 230 ATEX CSA IECEx TS Temperature catagories Ambient temperature C Medium Process temperature C T6 40 55 40 85 T5 40 70 40 100 T4 40...

Страница 37: ...irst Disconnect the power in 3 seconds and reconnect it again Then install LCM immediately Contact sales if it s still not solved LCM is not installed for a long time Instrument not update LCM status...

Страница 38: ...35000 4154 2 FLOAT32 PFC_2ND_PEAK_DISTANCE_MIN_VALUE 0 35000 4206 12 UINT8 PFC_PRODUCT_MODEL 24 4218 7 UINT8 PFC_PRODUCT_SERIAL 14 4225 4 UINT8 PFC_PRODUCT_DATE 8 4229 4 UINT8 PFC_HARDWARE_VERSION 8...

Страница 39: ...T16 PFC_4_MA 0 65535 4269 1 UINT16 PFC_20_MA 0 65535 4270 1 UINT16 PFC_SET2_4_MA 0 65535 4271 1 UINT16 PFC_SET2_20_MA 0 65535 4273 1 UINT16 PFC_LOCK_CURRENT_FLAG 0 1 4274 1 UINT16 PFC_SET2_LOCK_CURREN...

Отзывы: