BOOK 0959
33
Regulation percentages are of motor base speed under steady-state conditions
TABLE 11. SPEED REGULATION CHARACTERISTICS
VARIABLE
REGULATION
METHOD
Load
Change
(95%)
Line
Voltage
(±10%)
Field
Heating
(Cold/Normal)
Temperature
(±10
°
C)
Speed
Range
Standard Voltage
Feedback with IR
Compensation
2%
±1 %
5 - 12%
±2%
50:1
Optional Speed
(Tach) Feedback
a
0.5% ±1
%
0.2%
±2% 200:1
a. Unidirectional models only.
ADJUSTMENTS
1. Acceleration,
Linear....................................................................................................................0.1 - 30 Seconds
2. Deceleration,
Linear....................................................................................................................0.1 - 30 Seconds
3.
IR (Load) Compensation................................................................................................................ 0 - 10% Boost
4.
Jog Speed............................................................................................................. 0 - 100% of Motor Base Speed
5.
Maximum Speed ............................................................................................50% - 100% of Motor Base Speed
6.
Minimum Speed .................................................................................................... 0 - 40% of Motor Base Speed
7.
Torque (Current) Limit ........................................................................................ 0 - 150% of Full-Load Torque
SPECIFICATIONS
1. AC LINE PROTECTION -
A 100,000 ampere interrupting capacity AC line fuse provides instantaneous protection
from peak loads and fault currents. This line fuse is located inside the controller.
2. AUXILIARY CONTACT -
A normally-open Form A relay contact, rated .5 ampere @115 VAC and 2A at 30 VDC,
is available for external use. The relay energizes when a Run command is initiated, and de-energizes when a Normal
Stop command is initiated, the overload monitor trips, or the anti-restart circuit is activated.
3. FIELD SUPPLY -
A half-wave or full-wave shunt field supply is available as shown in Table 12, page 34.
Содержание 2601 Series
Страница 1: ......
Страница 2: ...BOOK 0959 SERIES 2610 MKII 2601 SINGLE PHASE ADJUSTABLE SPEED DC MOTOR CONTROLLERS 1 6 3 HP...
Страница 12: ...BOOK 0959 7 FIGURE 1 CONTROLLER MOUNTING CONFIGURATIONS...
Страница 13: ...BOOK 0959 8 FIGURE 2 CONTROLLER MOUNTING DIMENSIONS...
Страница 23: ...BOOK 0959 18 Blank Page...
Страница 27: ...BOOK 0959 22 Blank Page...
Страница 35: ...BOOK 0959 30 Blank Page...
Страница 40: ...BOOK 0959 35 SECTION VII DRAWINGS...
Страница 41: ...BOOK 0959 36 Figure 22 Functional Schematic Series 2610MKII 2601...
Страница 42: ...BOOK 0959 37 Figure 23 Series 2610MKII Control Board 1 6 3HP...
Страница 43: ...BOOK 0959 38 Blank Page...
Страница 46: ...www fincor nett...