Translation of the original instructions with assembly instructions AF 172 G2, Filtration Group GmbH, 09.12.17, Mat. No. 70355433, Version 05
Automatic valves (optional)
•
Connect the precontrol valve (5/2-way magnetic valve) to
the compressed air supply (approx. 6 bar).
•
Connect the solenoid to the power supply.
External pressure valve
•
Connect the solenoid to the power supply.
Refer to the contract documentation for
special versions.
1
2
bar
kPa
psi
R
P
S
A
B
R
P
S
A
B
Fig. 7:
Electro-pneumatic connections
Required on the switch box:
•
Manual release for cleaning
9.5.2 Connection to FG controller (optional)
•
Connect the incoming feeder, gear motor, external
pressure valve, differential gauge / switch (optional) and
precontrol valve (optional) in accordance with the
enclosed circuit diagram.
9.6
Control variants of the AF 172 G2
If the delta p signal is still present after
cleaning, the cleaning process is repeated.
The drain valve must remain closed for the
duration of the cleaning cycle.
The cleaning process is controlled differently according to
the application. The control variants described here are
examples and are simply intended to serve as a guide.
9.6.1 Control variant 1
B1
B2TH
B3
B4TL
B4TH
Fig. 8:
Control variant 1
Parameter
Description
Recommended
value
B1
Suppress differential
pressure peaks
1 s
B2TH
Motor running time
7 s
B3
External pressure valve
ON delay
0.5 s
B4TH
Drain valve pulse time
2 s
B4TL
Drain valve interval time
1 h
9.6.2 Control variant 2
B1
B2TH
B3
B7
B8
Fig. 9:
Control variant 2
Parameter
Description
Recommended
value
B1
Suppress differential
pressure peaks
1 s
B2TH
Motor running time
7 s
B3
External pressure valve
ON delay
0.5 s
B7
Drain valve starting
delay
5 s
B8
Drain valve pulse time
2 s
9.6.3 Other control options
Other control options, such as "continuous flushing" or
control adapted to the process sequence, can also be
implemented.
Electric line =
Pneumatic line =
Compressed
air
5/2-way
magnetic valve
5/2-way
magnetic valve
∆
p
Motor
Backflush
valve
External
pressure
valve
Drain valve
Interlocked
∆
p
Motor
Backflush
valve
External
pressure
valve
Drain valve
Interlocked