7.4

 

Wash time 

Defines the duration of the wash time per station. The following options can be selected: 

 

5-20 seconds in 1 second intervals 

 

20-55 seconds in 5-second intervals 

 

1-6 minutes in 0,5 minute intervals 

  

7.5

 

DP preset value 

  
In this field the user defines the value of the pressure difference between the inlet and outlet of 
the filter that, when reached, will cause the beginning of the wash cycle. This field appears only 
when the system includes the electronic DP sensor. 

When  pressure  is  expressed  in  BAR,  the  range  of  values  is  0.1  -  2.0  BAR.  When  pressure  is 
expressed in PSI the range of values is 1-30 PSI. 

When  the  system  does  not  include  the  electronic  PD  sensor.  but  an  external  PD  sensor  is 
connected, the flush request signal comes in the form of dry contact. 

 

7.6

 

Wash mode 

  
The wash mode defines how the wash cycles will be triggered. The options are as follows: 

 

OFF

 - There will be no washing 

 

By time

 - In this case the wash cycles will be repeated at a selected interval or triggered 

by the DP signal depending on which occurs first. No matter how the wash cycle started, 

the interval to the next cycle will start to be measured again after each end of the wash 

sequence. The selection ranges are as follows: 

-

 

5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 minutes 

-

 

2, 3, 4, 5, 6, 8, 12, 18, 24, 72, 120 hours 

 

DP

 - the wash will be triggered by DP only. 

-

 

5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 minutes 

-

 

2, 3, 4, 5, 6, 8, 12, 18, 24, 72, 120 hours 

 

DP

 - the wash will be triggered by DP only. 

  

* If the "+" and "-" keys are pressed and held simultaneously, the "Wash Mode" field will show 
the time remaining until the next cycle, alternatively, first hours and then minutes. 

 

7.7

 

Accumulations 

The  unit  accumulates  and  displays  the  number  of  wash  cycles  caused  by  DP,  by  time,  or 
manually.  In  each  of  the  accumulation  fields,  the  "+"  or  "-"  keys  can  be  used  to  clear  the 
accumulated value. 

U

SER 

M

ANUAL 

HYDRAULIC-200-H 

12 

Содержание HYDRAULIC-200-H

Страница 1: ...www itmfilters com Self cleaning Mesh Filter User manual HYDRAULIC 200 H Serial number _________________ Purchase date _________________...

Страница 2: ...3 Exploded view table 9 7 Control panel 10 7 1 Features listing 10 7 2 How to program the controller 11 7 3 The chain of editable fields 11 7 4 Wash time 12 7 5 DP preset value 12 7 6 Wash mode 12 7...

Страница 3: ...eplate 1 2 Basic concepts Filtration surface Area that allows water to pass while retaining suspended particles Recommended flow Optimal filtration must take into account the quality of the source wat...

Страница 4: ...dance with the applicable European Directives Directive 2006 42 CE on Machines Annex IIA Directive 2014 68 EU on Pressure Equipment and Directive 2014 35 EU on Electrical Material These quality requir...

Страница 5: ...ge 10 585 323 273 195 14135 235 177 HYDRAULIC 212 H COMPACT Flange 12 645 355 300 215 14135 235 181 TABLE 1 Manufacturing technical characteristics Materials o Carbon steel metal components o Zinc pla...

Страница 6: ...C 206 H 355 1455 352 900 203 1865 400 1300 HYDRAULIC 208 H COMPACT 355 1455 352 900 203 1865 400 1300 HYDRAULIC 208 H 355 1741 438 1100 203 2150 400 1585 HYDRAULIC 210 H COMPACT 355 1741 438 1100 203...

Страница 7: ...operation with automatic cleaning OPEN cleaning cycle CLOSE filter operation without automatic cleaning USER MANUAL HYDRAULIC 200 H 5 IMAGE 4 SOLENOID CALIBRATED ORIFICE HYD REL MANUAL ACTUATOR SUCTIO...

Страница 8: ...ge When the mesh filter becomes clogged it produces a pressure difference between the inlet and outlet manifolds The automatic cleaning cycle starts when it reaches a pressure difference of 0 3 kg cm...

Страница 9: ...nology used in the manufacture of the HYDRAULIC 200 H filter offers high filtration surfaces with compact lengths due to the maximization of the filter cartridge 6 Maintenance and spare parts 6 1 Main...

Страница 10: ...ilters com you can find a video tutorial with the maintenance process 6 2 Exploded view USER MANUAL HYDRAULIC 200 H 8 23 25 24 20 30 29 28 27 26 33 32 31 34 17 22 21 1 2 3 4 5 6 7 3 8 9 11 10 12 13 15...

Страница 11: ...rogrammer 1 1 1 1 28 Filter Cartridge 1 HYD 204 H 04 00 1 HYD 206 H 04 00 1 HYD 208 H 04 00 1 HYD 210 H 04 00 29 Centering Disk 1 HYD 206 H 05 07 1 HYD 206 H 05 07 1 HYD 206 H 05 07 1 HYD 206 H 05 07...

Страница 12: ...ump The AC model contains an internal transformer that can be powered by 110V or 220V from which 24v AC is generated for the solenoids The wash cycles can be triggered either by time or by means of th...

Страница 13: ...ntered the user will not be able to go back and must keep pressing the ENTER key repeatedly to go through the chain of editable fields until reaching the WASH TIME field again Please note that before...

Страница 14: ...ash cycles will be triggered The options are as follows OFF There will be no washing By time In this case the wash cycles will be repeated at a selected interval or triggered by the DP signal dependin...

Страница 15: ...roblem The options are 1 10 or no which means to ignore the loop problem Yes No assigning an output for alarm activation Yes No assigning an output for Delay Valve activation This is a special mode th...

Страница 16: ...start from the beginning instead of continuing from the stop point 7 11 Connecting the DP sensor to the filter system The DP sensor is connected to the filter system by 2 command tubes one that comes...

Страница 17: ...www itmfilters com 7 14 Timing diagram Without delay valve With delay valve Main valve Valve 1 Valve 2...

Страница 18: ...The external DP sensor is optional and is intended to be used in cases where the integrated electronic DP sensor is not included 2 The unit can be powered by 6v DC or 12v DC 3 The solenoids are 12v D...

Страница 19: ...ensor is optional and is intended to be used in cases where the integrated electronic PD sensor is not included 2 The unit is powered by 24v AC transformed from 220 110 v AC 3 In the solenoids it will...

Страница 20: ...ted analog electronic DP sensor or external dry contact DP sensor Pressure sensor Dry contact pressure sensor Operating temperature AC model 0 60 C Power source 220 or 110 v AC 50 or 60 Hz with includ...

Страница 21: ...ablished quality or is outside the specifications indicated in the technical tables vi A use of flow discordant with the water quality according to the parameters defined in the technical tables vii P...

Страница 22: ...www itmfilters com INTRAMESA MZ S A Pol gono Armentera P 99 22400 Monz n Huesca www itmfilters com info itmfilters com Tel 974 10 50 05...

Отзывы: