26-1369-01
15
LED Table
LED Label
Pattern
Indication
State
Disabled
Fast Blink
SRM Disabled.
Disabled
Off
SRM Enabled.
Normal
Release
Fast Blink
Agent Released.
Released
Off
Agent not Released.
Normal
Discharge
Pressure
Fast Blink
Discharge pressure is high.
Release in process
Slow Blink
Discharge pressure switch wire short fault.
Fault
Very Slow Blink
Discharge pressure switch wire open fault.
Fault
Off
Discharge pressure is normal and wiring is good.
Normal
Bottle
Pressure
Fast Blink
Bottle pressure is low.
Fault
Slow Blink
Bottle pressure switch wire short fault.
Fault
Very Slow Blink
Bottle pressure switch wire open fault.
Fault
Off
Bottle pressure is normal and wiring is good.
Normal
Solenoid
Missing
Fast Blink
Release Tamper input activated
Fault
Slow Blink
Release Tamper input wire short fault.
Fault
Very Slow Blink
Release Tamper input wire open fault.
Fault
Very Slow Double
Blink
Solenoid coil open fault.
Fault
On Continuous
Solenoid coil short fault.
Fault
Off
No faults on Solenoid coil and Release Tamper
input is in Normal state.
Normal
Power
Fault
Fast Blink
External power is low.
Fault
Off
External Power is good.
Normal
Fault
Fast Blink
A Fault condition is present on the SRM.
Check other LEDs to determine the Fault type.
Fault
Off
No Fault present on the SRM.
Normal
Comms
Off
The SRM is not functional.
Fault
Momentary Blink
every 5 seconds
The SRM is functional and communicating with the
SRP panel.
Normal
Fast Blink – LED blinks once every ¼ second.
Slow Blink – LED Blinks once every 2 seconds.
Very Slow Blink – LED Blinks once every 5 seconds.
Very Slow Double Blink – LED Blinks twice every 5 seconds.