26-0510 Issue 6
Technical Data
Dimensions
Width ....................................................... 89 mm
Height ...................................................... 89 mm
Flush Depth Protruding ........................... 34 mm
Surface Depth ......................................... 62 mm
Operating Temperature
. ................................................................ -10
o
C to +50
o
C
Voltage Ranges
DC Output from Mains Powered Panel ... 25.5 to 35V DC
DC Output from Battery Powered Panel . 20 to 26V DC
Operating Current (Typical)
Quiescent ................................................ 185 uA
End of line ON if applicable ..................... 175 uA
(in addition to Quiescent)
Alarm Sounding – Sounder High ............. 14.5 mA
Alarm Sounding – Sounder Low ............. 12.6 mA
Loading Units (SLUs)
V3 Panel
Pro Panel
Max Loading Units per zone ................... 27 SLU .......... 160 DLU
Sounder High. ......................................... 2.5 SLU ......... 14.5 DLU
Sounder Low ........................................... 2.0 SLU ......... 13.0 DLU
Volume Level
Sounder High .......................................... 85+ dB(A)
(@ 1m anechoic, Dual Tone)
Sounder Low ........................................... 65+ dB(A)
Flammability
. ................................................................ UL94-V2
IP Rating
. ................................................................ IP 21C