FIK-UV-IR-HD
User Manual
Doc. No. 06-935.02
For more information & Technical support: (800)-979-FIKE (3453)
26
B.2
False Alarm Immunity
The following table shows test results of false alarm immunity for detectors configured to “Extreme”
sensitivity. For each radiation source a distance is listed. This is the minimum tested distance, from which the
detectors did not alarm when exposed to the radiation source (either modulated or non-modulated).
False Stimuli at Extreme Sensitivity
False Alarm Source
Modulated
Unmodulated
Distance ft (m) Response
Distance ft
(m)
Response
Sunlight, Direct,
Reflected
No Alarm
No Alarm
Incandescent
frosted glass light,
300W
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Fluorescent, 70W
(3x23.3W)
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Electric arc
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Arc welding
10 (3)
No Alarm
10 (3)
No Alarm
Radiation heater,
2000W
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Halogen lamp
(500W) non-
shielded
10 (3)
No Alarm
10 (3)
No Alarm
Halogen lamp
(1000W)
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Mercury vapor lamp
160Wx3
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Exhausts
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Projector led
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Solenoid bell
2 (0.6)
No Alarm
2 (0.6)
No Alarm
soldering iron
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Electric Drill
2 (0.6)
No Alarm
2 (0.6)
No Alarm
Contact us
Fike Corporation
704 SW 10th St, Blue Springs, MO 64014, USA
Tel: (+1) 816-229-3405
www.Fike.com