FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Network Management
Network Programming
6.2.4 Computer Access
An installer at the panel site can initiate communications between the panel and a computer running the HFSS Programming Tool (see also
Section 10.5). In order for this communication to function properly, both the computer (running the software) and the control panel must
have matching computer access numbers and computer codes.
To program computer access information:
1.
Enter the Installer Code. The panel will automatically go to the Main Menu.
2.
Select 6 for Network Programming.
3.
Press 4 to enter the Computer Access Menu.
4.
Enter the computer access number (up to 6-digits), then press ENTER.
5.
Enter the computer code, then press ENTER.
6.2.5 Access Codes
Access codes provide the user access to the control panel functions. Each Access Code can be customized for each user. This allows some
users the ability to access programming and other higher level panel functions, while other users may only need access to lower level func-
tions such as preforming fire drills, or acknowledging trouble conditions.
Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to. Because this is the profile for a key, the user name and
the Access Code can not be edited for this profile.
Profile 2 is the profile for the installer and is referred to as the “Installer Code”. This profile’s user name and panel functions can not be
edited. Table 6.1 lists the panel functions that can be selected for each user profile.
*Function Keys are only available on the FIK-RA2000 LCD annunciator
To change an Access Code:
1.
Enter the installer code. The panel will automatically go to the Main Menu.
2.
Select 6 for Network Programming Menu.
3.
Select 5 for Access Codes.
The Display reads:
Select Profile 01
Fire Fighter’s Key
Type of Function
Selectable Functions
Panel Operations
System Reset
System Silence
System Ack
Fire Drill Key
*F1 Function Key
*F2 Function Key
*F3 Function Key
*F4 Function Key
Panel Menus
System Tests
Fire Drill Menu
Indicator Test
Walk Test-No Report
Walk Test -With Report
Communicator Test
Clear History Buffer
Point Functions
Disable/Enable Point
Point Status
Set SLC Device Address
SLC Single Device Locater
SLC Multiple Device Locater
I/O Point Control
Event History
Set Time & Date
System Information
Network Diagnostics
Network Programming
Panel Programming
Send/Receive Firmware Update
Table 6.1
:
User Profile Selectable Panel Functions