Operation Mode Behavior
System Operation
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
105
Figure 10.4 Ethernet Information Screen
AlarmNet Info
1.
Press 6 from the System Information Menu for AlarmNet Info.
2.
Cell Strength: 0 to 100% .
3.
Status: Registered/Not Registered.
AlarmNet Temp Pin
1.
Press 7 from the System Information Menu for AlarmNet Temp Pin. This is used in case the FACP is replaced on the CCP.
10.5 Operation Mode Behavior
The control panel can be in one or more of seven conditions at any given moment: Normal, Alarm, Prealarm, Supervisory, Trouble, Silenced,
and Reset. Table 10.1 describes the behavior of the panel in each of these modes.
When looking at the LCD, the screen will display FIRE for the “Fire System”, CO for the “CO System”. The highest priority event will dis-
play first and include the event count (see Figure 10.6).
Press the down arrow to view the location and type of alarm, supervisory or trouble. If the panel is programmed to Auto Display Event,
information describing the highest priority active event will display on the first two lines. The 3 and 4th line will show the status of which
event types are active for each system (fire and CO). Auto Display Event activates after two minutes of annunciator inactivity.
Figure 10.5 Highest Priority Event Display
Figure 10.6 This Screen will display when more that 3 event types are active