TECHNICAL INFORMATION FOR CDM4160

Table 5 - Signal output in operation mode

3.  Operation modes

3-1  Warm up

The sensor is warmed up for two hours after the 

module is powered on. The green LED blinks on and 

off and a constant voltage (0.4V for -L00, 0.2V for -M00, 

0.04V for -H00) is output from the concentration output 

port during this period. The green LED will be lit 

continuously after the warm-up period ends unless 

a power outage occurs.

3-2  CO

2

 concentration lower than threshold level 

The green LED will be on if the calculated CO

2

 

concentration is lower than the threshold level.

3-3  CO

2

 concentration exceeds threshold level

The red LED will be lit and the control signal output 

is turned “ON” if the concentration exceeds the 

threshold level.

The control signal output is turned to “OFF” and the 

red LED will be off when CO

2

 concentration drops 

to 90% of the threshold level.

3-4  Trouble

When the sensor's output is abnormal, the yellow 

LED blinks on and off and the TRBL signal is set to 

“ON.

4.  Cautions

1) By assuming that the baseline level represents 

fresh air (400ppm of CO

2

), actual CO

2

 concentrations 

are calculated based on the difference between the 

baseline level and the current sensor output. As a 

result, the following cautions should be noted:

a) Accurate readings cannot be expected if an accurate 

baseline could not be acquired.

b) The sensor should be exposed to fresh air 

periodically to properly renew the baseline level. 

Performance shown in the specifications cannot be 

achieved if the module was used in an environment 

where CO

2

 concentrations increased slowly and 

steadily for a long period of time.

c) The module should be located in fresh air during 

the warm-up period. Accurate readings cannot be 

expected until the baseline is acquired in fresh air. If 

the module is warmed up in an environment where 

CO

2

 concentration is higher than normal fresh air, the 

baseline will represent a polluted level and the device 

will not be able to clean the air sufficiently.

d) Power should be on at all times. Since the baseline 

is memorized in a microcomputer, if the power should 

be cut off, the memory would be lost and operation 

would resume from the warm-up process.

e) The module is not intended for usage in life saving 

equipment. If the module is incorporated into life 

saving equipment, an alternative and secure measure 

for calculating CO

2

 concentration should be used be 

used for the life safety function.

2) This module is designed only for indoor usage. 

The module should be protected from exposure to 

rain, wind, sun, heat radiation, etc.

3) Please apply a regulated voltage, otherwise the 

accurate reading cannot be expected. Application 

of excessive and/or reverse voltage would cause 

damage to the module.

4) The module does not include a circuit for protection 

from excessive current. An excessive current 

protection circuit should be added to a peripheral 

circuit of the module. 
5) The sensor may deteriorate if it is stored without 

power in a high humidity environment for a long 

period of time. Please keep the sensor in a humidity-

proof bag with a desiccant if the sensor is to be stored 

without power for a long period of time.
6) The sensor has dependency on oxygen concentration. 

Under environments where the oxygen concentration 

Condition

Green LED

Yellow LED

Red LED

Control signal 

(CTRL)

Trouble signal 

(TRBL)

CO

2

 concentration signal

CDM4160-L00 CDM4160-M00 CDM4160-H00

Warm-up period

Blink ON/OFF

OFF

OFF

OFF

OFF

0.4V

0.2V

0.04V

CO2 conc < threshold

ON

OFF

OFF

OFF

OFF

CO

2

 conc/1000

CO

2

 conc/2000

CO

2

 conc/10000

CO2 con > threshold

ON

OFF

ON

ON

OFF

CO

2

 conc/1000

CO

2

 conc/2000

CO

2

 conc/10000

Trouble

ON

Blink ON/OFF

OFF

OFF

ON

4.5V

4.5V

4.5V