The final RSNetworx Configuration should look similar to this:
Appendix C.2.3.
Testing
The SlotServer should now be visible to the CPU.
Go Online with RSLogix and check the Input buffer of the SlotServer for data.
Examine offset 2 of the input tag for a non-Zero value. If the SlotServer is multiplexing (DA_Count >1), then
this value will be cycling through the Buffer numbers; if DA_Count=1, then offset 2 will be fixed at 1.
If offset 2 is zero, then the SlotServer is not being seen by the CPU, and Diagnostics will need to be performed
using RSNetWorx and RSLogix to determine the cause of the problem.