SlotServer Configuration Manual
Page 22 of 37
ProSoft Technology, Inc. is the exclusive provider of FieldServer SlotServers.
For Technical Support call +1 661.716.5100
Appendix B.
TROUBLESHOOTING
Appendix B.1.
SlotServer block number [ 0 ] out of range!
It is necessary to put a non-zero buffer number in offset 2 of the output buffer, or to remove the related Map
Descriptor if output buffers are not being used. Refer also to Appendix B.2.
Appendix B.2.
Driver Error screen returns “Illegal Protocol” Error.
Ensure that the configuration is not set to write to offset 0 of the output buffer. Offsets 0, 1 and 3 should be
clear and the correct non-zero buffer number should be written into offset 2.
If the output buffer is not being used then the corresponding Logix Map descriptor should be removed.
Appendix B.3.
SlotServer output image data transfer stops after a few hours when keeping RSWho open
to browse the rack.
This has been addressed in V1.04aB of the driver. Upgrade to V1.04aB or later.