5.1.4. Map
Descriptor
Example 2: IO Write
This Map Descriptor makes the memory area writable which was made readable by the previous Map Descriptor.
Thus memory area can be made read only, write only or read and write enabled.
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name
Address
Length
Data_Type
Command_Name
Unit_number
SRV_CIOw,
DA_CIO,
0,
SERVER,
PLC1,
0,
6143,
CIO-WORD
MEMORY AREA WRITE
0
5.1.5.
Map Descriptor Example 3: Clock Read:
This Map Descriptor enables the Driver to serve the client with a Clock read request. See Appendix B.1for further
information
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name
Length
Command_Name
Unit_Number
SRV_CLKr,
DA_CLKr,
0,
SERVER,
PLC1,
7,
CLOCK READ
0s
5.1.6.
Map Descriptor Example 4: Clock Write:
This Map Descriptor enables the Driver to update Clock information when the Client makes a Clock Write request. See
section Appendix B.1 for further information.
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_name
Length
Command_Name
Unit_Number
SRV_CLKr,
DA_CLKr,
0,
SERVER,
PLC1,
7,
CLOCK WRITE
0
5.1.7.
Map Descriptor Example 5: CPU Cycle Times:
This Map Descriptor enables the Driver to serve Clients with CPU cycle time information upon request. See Appendix
B.1 for further information.
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name
Length
Command_Name
Unit_Number
SRV_CYCT,
DA_CYCT,
0,
SERVER,
PLC1,
7,
CLOCK READ
0