Communications Status LED’s
LED
Description
Run
When the SlotServer is powered up, this light will start flashing after approximately 2
minutes. If this light does not flash, it is an indication that the firmware is not running,
and that the SlotServer will not be operating.
LonSvc
This light will flash when the card’s Neuron chip is unconfigured, and will extinguish
when the SlotServer has been commissioned into a Network.
NodeOff
This light indicates that a device bound to the SlotServer on the LonWorks network is
not communicating. Use the LonWorks Network Manager to troubleshoot the problem.
Conf
Err
This light indicates an error in the card configuration. Since this model is shipped pre-
configured, this light should not come on unless the card configuration is tampered with
Sys Err
This light indicates that an unexpected operation state occurred. The light can be reset
by cycling power to the card. If the error re-occurs persistently, then contact FieldServer
Technical support for assistance with troubleshooting after setting up the trade port as
shown in Appendix A.
Com Err
This light indicates that a communication error occurred. Use the LonWorks NetWork
Manager to troubleshoot the problem, or refer to Appendix A.
TP/FT10 LonWorks connection
This two wire connection is polarity insensitive and can be multi-dropped into a LonWorks
Network.
Trade Port
The Trade port is an Ethernet port that can be used for advanced troubleshooting (See
Appendix A). Use standard Ethernet cables for this connection.
4.2.
Inside Cover Door Label
A label has been provided on the inside of the cover door for the User to document
important or useful configuration parameters used. In particular, special provision has been
made to document the Trade port IP parameters, as well as the LonWorks DSN
(Domain/Subnet/Node) allocated by the Network Manager. These fields are there to be
utilized at the User’s discretion.