FS-RA-CLX-LON-000_SlotServer_LonWorks_Open_Interface_(T17010)
Page 19 of 28
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldServer.com
Tel
: (408) 262-2299
Fax
: (408) 262-2296
Toll_Free
: 888-509-1970
Very Important Note!
It is very important to only update all the data of the Output Image Tag once using a
Synchronous File Copy element. It is not permissible to update the block number into the
Output Image Tag and then the data as this will cause an asynchronous transfer of data.
6.3.
Optimizing performance for smaller applications
If less than the full number of Function Blocks is needed, it is advisable to trim the Preset
value in the CTU element in the full SlotServer RSLogix project to the maximum block value.
The blocks should be used starting from 0 upwards. This will ensure that update rate is kept
as short as possible.