Appendix D.3.
Error Codes
General
Status
Extended
Status
Description
0x01
0x0100
Connection in Use or Duplicate Forward Open.
0x01
0x0103
Transport Class and Trigger combination not supported
0x01
0x0106
Ownership conflict
0x01
0x0107
Connection not found at target application.
0x01
0x0108
Invalid Connection Type. Indicates a problem with either the Connection Type or
Priority of the Connection.
0x01
0x0109
Invalid connection size
0x01
0110
Device not configured
0x01
0x0111
RPI not supported. May also indicate problem with connection time-out multiplier
or production inhibit time.
0x01
0x0113
Connection Manager cannot support any more connections
0x01
0x0114
Either the Vendor Id or the Product Code in the key segment did not match the
device
0x01
0x0115
Product Type in the key segment did not match the device
0x01
0x0116
Major or Minor Revision information in the key segment did not match the device
0x01
0x0117
Invalid Connection Point
0x01
0x0118
Invalid Configuration Format
0x01
0x0119
Connection request fails since there is no controlling connection currently open.
0x01
0x011A
Target Application cannot support any more connections
0x01
0x011B
RPI is smaller than the Production Inhibit Time
0x01
0x0203
Connection cannot be closed since the connection has timed out
0x01
0x0204
Unconnected Send timed out waiting for a response.
0x01
0x0205
Parameter Error in Unconnected Send Service
0x01
0x0206
Message too large for Unconnected message service
0x01
0x0207
Unconnected acknowledge without reply
0x01
0x0301
No buffer memory available
0x01
0x0302
Network Bandwidth not available for data
0x01
0x0303
No Tag filters available
0x01
0x0304
Not Configured to send real-time data
0x01
0x0311
Specified Port Not Available – the FieldServer is trying to open a connection but
the target port is not available at the remote device. This can be resolved by using
the correct EIP_Path parameter.
0x01
0x0312
Link Address specified in Port Segment Not Available
0x01
0x0315
Invalid Segment Type or Segment Value in Path
0x01
0x0316
Path and Connection not equal in close
0x01
0x0317
Either Segment not present or Encoded Value in Network Segment is invalid.
0x01
0x0318
Link Address to Self Invalid
0x01
0x0319
Resources on Secondary Unavailable
0x01
0x031A
Connection already established
0x01
0x031B
Direct connection already established
0x01
0x031C
Miscellaneous
0x01
0x031D
Redundant connection mismatch
0x01
0x031D
No more consumer resources available in the producing module
0x01
0x031E
No connection resources exist for target path
0x01
0x0320-
Vendor Specific