4.1.34.
System Control Commands containing no Parameters: Simulate wallstation(s) switch release
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
DA_Lut_List,
DA_Lut_List_Offset,
Length
Ws_sw_rls,
Lut_triggers,
17,
awt,
LUT_GRF6_0,
sim_ws_sw_rls,
Sim_sw_list,
0,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
Link number ( 0-11 )
1
Station of link ( 0-31 ) of Switch ID 0
2
Switch on station ( 0-31 ) of Switch ID 0
3
Station of link ( 0-31 ) of Switch ID 1
4
Switch on station ( 0-31 ) of Switch ID 1
.. ..
63
Station of link ( 0-31 ) of Switch ID 31
64
Switch on station ( 0-31 ) of Switch ID 31
Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.
4.1.35.
System Control Commands containing no Parameters: Stop scene ramp down
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
DA_Lut_List,
DA_Lut_List_Offset,
Length
Stop_scn_rmp_dn,
Lut_triggers,
18,
awt,
LUT_GRF6_0,
stop_scene_ramp_dn,
Area_list,
0,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0-31
Area(s) with scenes to stop ramp down
Note: After setting up the area numbers to stop scene ramps in the DA_Lut_List Data Array, trigger this command by writing the number of areas
into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.