![FieldServer FS-8700-84 Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/fieldserver/fs-8700-84/fs-8700-84_driver-manual_2287949016.webp)
FS-8700-84_Lutron_eLumen Driver Manual
Page 13 of 36
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldServer.com
Tel
: (408) 262-2299
Fax
: (408) 262-9042
Toll_Free
: 888-509-1970
4.1.9.
System Monitor Command – Serial Number
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name,
GRAFIK_command,
Length
Serial_num,
5s,
Serial_num,
0,
rdbc,
LUT_GRF6_0,
serial_no,
1
Data storage in Data Array
Position from offset
Description
0 Serial
number
4.1.10. System
Monitor Command – Area Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Scan_Interval, Data_Array_Name,
Data_Array_Offset, Function,
Node_Name,
GRAFIK_command,
Area,
Length
Area_sts_00,
1s,
Area_status,
0,
rdbc,
LUT_GRF6_0,
Area_status,
0,
2
Area_sts_01,
1s,
Area_status,
2,
rdbc,
LUT_GRF6_0,
Area_status,
1,
2
Data storage in Data Array
Position from offset
Description
0
System scene on status
1
Sequence running status
Note: This command stores 2 data values. To prevent overlaps, remember to increment Data_Array_Offset by 2 when referencing the same Data
Array with other Map Descriptors.