FS-8700-47 DNP 3.0 Driver Manual
Page 44 of 51
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
considered to be selected and the operation can proceed. If the value is zero, the driver rejects the
command. If the secondary Data Array is not specified, the port is considered to be permanently
selected.
The driver supports the following Control Codes
Code Operation Supported
0
Null
No
1
Pulse On
No
2
Pulse Off
No
3
Latch On
Yes
4
Latch Off
Yes
5-15
Undefined
N/A
‘Direct Operate’ and ‘Direct Operate with No Acknowledgement’ Commands
The driver does not check if the data object had previously been selected. The supported Control
Codes are described above.
Analog Output Block
When a ‘Select’ command is received the driver sets the select flag in a secondary Data Array
defined by the “DA_Bit_Name” parameter, if available. When any of the operate commands are
received the driver stores the value sent with the command in the Data Array defined on the Map
Descriptor.
Control Relay Block (Object=12)
If the Control Code is supported the driver does the required action.
The driver supports the following Control Codes
Code Operation Supported
0
Null
Not Supported
1
Pulse On
Not Supported
2
Pulse Off
Not Supported
3
Latch On
Driver sets Data Array value to ‘1’
4
Latch Off
Driver sets Data Array value to ‘0’
5-15
Undefined
N/A
If the “DA_Bit_Name” parameter is specified then the driver stores the control code as extracted from
the command and if the “DA_Byte_Name” is specified then the driver stores the count field, extracted
from the command message.
Pattern Control Block
Object 12 variations 2 & 3 are not supported by the driver.