FS-8700-39 EST3 Driver Manual
Page 25 of 25
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Driver Error Messages
Error Message
Description and Action Required
EST3:#01 FYI. For an Old
EST3 Panel, Read MD length
must be even.
This message will be displayed once if any Map Descriptor in a configuration file has an odd
length. Old EST3 Panels (before 2002) simply do not communicate if length is odd.
This message can be ignored if it is new EST3 panel. But if it is old or unknown, try changing
the Map Descriptor length to an even value before contacting technical support.
EST3:#02 Err. Read MD
length must > 0 and <= %d
Numbers of addresses to be read per request are limited.
Edit configuration file to set Map Descriptor length within specified range.
7
EST3:#03 Err. Write MD
must have length = 1
One Map Descriptor can write only 1 value. Change length to 1
7
.
EST3: #04 Unknown Escape
Sequence
1B
%02X
considered as %02X
This message is printed if the FieldServer receives sequences that are not specified.
Specified sequences are 1B 82, 1B 8D and 1B 9B. This message is for information only and
can be ignored unless the data stored by the FieldServer is invalid in which case, call Tech
support.
7
Upload the configuration file, make the necessary changes, download to the FieldServer and cycle power to the FieldServer for the changes to take effect.