Driver Version: 

1.02 

Document Revision:   3 

 

 

A Sierra Monitor Company

APPLICABILITY & EFFECTIVITY 

Effective for all systems manufactured after March 2010 

 

Driver Manual  

(Supplement to the FieldServer Instruction Manual)

 

 

FS-8700-130 Notifier NCA2-NFS2-3030

 

Содержание FS-8700-130

Страница 1: ...cument Revision 3 A Sierra Monitor Company APPLICABILITY EFFECTIVITY Effective for all systems manufactured after March 2010 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 130 Notifier NCA2 NFS2 3030 ...

Страница 2: ... Mapping 7 5 2 Client Side Connection Parameters 9 5 3 Client Side Node Parameters 9 5 4 Client Side Map Descriptor Parameters 10 5 4 1 FieldServer Related Map Descriptor Parameters 10 5 4 2 Driver Related Map Descriptor Parameters 10 5 4 3 Map Descriptor Example Standard example 11 6 Configuring the FieldServer as a Notifier NCA2 NFS2 3030 Server 12 Appendix A Useful Information 13 Appendix A 1 N...

Страница 3: ...itored by third party tools Since the FieldServer does not actively poll for data the accuracy and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues If a networked panel does not send the CLEARED message for latched points via the NCA2 it is not possible to detect cleared points unless a system reset is done It is possible to configure...

Страница 4: ...n drawing Configure the Notifier Panel according to manufacturer s instructions FieldServer FieldServer Part 8917 16 Pigtail for RJ45 Port RJ45 Connection to TB5 Printer Port Notifier NCA2 NFS2 3030 Connect to one of the RS 232 Ports on the FieldServer P1 CTX CRX REF PTX PRX REF TB5 Printer CRT Rx Brown Tx Orange White Com Blue White 1 8 Connector Pinouts TB5 CRT Function Receive Reference Transmi...

Страница 5: ...l 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 3 1 Hardware Connection Tips Hints The FieldServer should preferably be connected to the TB5 Printer port It is theoretically possible to connect to the TB5 CRT port but this has not been fully tested The Panel s port must be enabled and set to 80 Columns Not Supervised ...

Страница 6: ...ion Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format FLOAT BIT UInt16 SInt16 Byte Packed_Byte Swapped_Byte Data_Array_Length Number of Data Objects Must be larger than the data storage area required by the Map Descriptors for the data be...

Страница 7: ... the FieldServer This section documents and describes the parameters necessary for configuring the FieldServer to receive information from a Notifier Panel 5 1 Panel Status Memory Mapping The primary purpose of this driver is to record the status of devices connected to the Notifier panel by interpreting the text messages sent to the printer or CRT port Not all messages will be interpreted as many...

Страница 8: ...Active 1432 1590 ON OFF 1591 1749 Memory Type Detector_Trouble Module_Trouble Troubles Faults 1 159 Parameter Addresses For each Node Memory Type Node_Trouble Troubles Faults 1 508 Memory Type Panel Panel Maximum12 Boards and 8 Panel circuits per Board Hardware address memory address Board 1 panel 1 1 Board 1 panel 2 2 Board 2 panel 1 9 Board 12 panel 8 96 Fire Alarm 1 96 Security Life 97 192 Life...

Страница 9: ...ts Specify data bits 8 Vendor limitation Stop_Bits Specify stop bits 1 Vendor limitation Example Client Side Connections Connections Port Protocol Baud Stop_Bits Parity P8 nfs2 nca 9600 1 None 5 3 Client Side Node Parameters Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Node_ID Station address of any physical Node on network...

Страница 10: ...iptor Parameters Column Title Function Legal Values Node_Name Name of Node to fetch data from One of the Node names specified in Section 5 3 Data_Type Specify memory area type Detector Module Detector_Trouble Module_Trouble Panel Panel_Trouble Bell_Trouble Node_Trouble Address Starting address of block As per Data_type Detector Module 1 1749 Detector_Trouble Module_Trouble 1 159 for point troubles...

Страница 11: ..._N2_Troubles DA_SYS_N2 0 Passive NODE2 Node_Trouble 1 508 SMD_N2_PANEL DA_N2_PANEL 0 Passive NODE2 Panel 1 1056 SMD_N2_PANEL_T DA_N2_PANEL_T 0 Passive NODE2 Panel_Trouble 1 96 SMD_N2_BELL_T DA_N2_BELL_T 0 Passive NODE2 Bell_Trouble 1 4 SMD_N2L01D DA_N2L01D 0 Passive NODE2 1 Detector 1 1749 SMD_N2L01D_T DA_N2L01D_T 0 Passive NODE2 1 Detector_Trouble 1 159 SMD_N2L01M DA_N2L01M 0 Passive NODE2 1 Modu...

Страница 12: ...logies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 6 CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2 NFS2 3030 SERVER This driver cannot be configured as a Server ...

Страница 13: ...Appendix A 3 Driver Limitations and Exclusions Zone information will not be recorded To synchronize the FieldServer with the panel connect the running FieldServer and press the System Reset button on the panel All current events will be re sent to the FieldServer The port must be enabled on the unit and set to 80 columns with NO supervision All data related to non event driven reports will not be ...

Страница 14: ...ground potential problems Appendix B 2 Networking Tips By default FieldServer does not take any action on receiving a SYSTEM RESET Normally when a Node initiates SYSTEM RESET by pressing the RESET button on the Panel the panel sends an individual CLEAR message for every point it clears in its memory area The FieldServer therefore waits for the CLEAR message to clear a specific bit in its memory fo...

Страница 15: ...ates 1 0 SECURITY ALARM CLEARED SECURITY ALARM states 1 0 CRITICAL PROCESS CRITICAL PROCESS states 1 0 SUPERVISORY CLEARED SUPERVISORY states 1 0 TROUBLE FAULT CLEARED TROUBLE FAULT States counter DISABLED CLEARED DISABLED states 1 0 PREALARM CLEARED PREALARM states 1 0 ACTIVE CLEARED ACTIVE states 1 0 ON OFF OFF states 1 0 SYSTEM NORMAL Resets all addresses in all memory areas but only if data is...

Страница 16: ...D 5 276 STYLE 6 NEG LOOP 10 23 COMM FAULT LOOP INTERFACE BOARD 6 277 STYLE 6 POS LOOP 1 24 COMM FAULT LOOP INTERFACE BOARD 7 278 STYLE 6 POS LOOP 2 25 COMM FAULT LOOP INTERFACE BOARD 8 279 STYLE 6 POS LOOP 3 26 COMM FAULT LOOP INTERFACE BOARD 9 280 STYLE 6 POS LOOP 4 27 COMM FAULT LOOP INTERFACE BOARD 10 281 STYLE 6 POS LOOP 5 28 CATASTROPHIC ISIB COMMUNICATIONS FAULT 282 STYLE 6 POS LOOP 6 29 MEM...

Страница 17: ...BOVE LIMIT ON LOOP 10 335 REMOTE DISPLAY 2 TROUBLE 82 TOO MANY DEVICES ON LOOP 1 336 REMOTE DISPLAY 3 TROUBLE 83 TOO MANY DEVICES ON LOOP 2 337 REMOTE DISPLAY 4 TROUBLE 84 TOO MANY DEVICES ON LOOP 3 338 REMOTE DISPLAY 5 TROUBLE 85 TOO MANY DEVICES ON LOOP 4 339 REMOTE DISPLAY 6 TROUBLE 86 TOO MANY DEVICES ON LOOP 5 340 REMOTE DISPLAY 7 TROUBLE 87 TOO MANY DEVICES ON LOOP 6 341 REMOTE DISPLAY 8 TRO...

Страница 18: ...NNUN 6 NO ANSWER 138 LIB 8 NIB COMMUNICATION ERROR 392 ANNUN 7 NO ANSWER 139 LIB 9 COMMUNICATION ERROR 393 ANNUN 8 NO ANSWER 140 LIB 10 NIB COMMUNICATION ERROR 394 ANNUN 9 NO ANSWER 141 LIB 1 NIB M S PROGRAMMING ERROR 395 ANNUN 10 NO ANSWER 142 LIB 2 NIB M S PROGRAMMING ERROR 396 ANNUN 11 NO ANSWER 143 LIB 3 NIB M S PROGRAMMING ERROR 397 ANNUN 12 NO ANSWER 144 LIB 4 NIB M S PROGRAMMING ERROR 398 A...

Страница 19: ...R SECONDARY STATUS 450 UDACT NO ANSWER 197 LINK PROTECTOR PRIMARY NOT PRESENT 451 MASTER BOX NO ANSWER 198 EVENT BUFFER 80 FULL 452 DAA NO ANSWER 199 EBI STATUS 453 NO ANSWER 200 SOFTWARE MISMATCH 454 NETWORK FAILURE 201 NO POWER SUPPLY INST 455 WORKSTATION FAN FAILURE 202 TEST PROGRAM UPDATE 456 UPS FAILURE 203 HISTORY 80 FULL 457 NCM COMM FAILURE 204 FLASH IMAGE ERROR 458 NODE COMMUNICATIONS FAI...

Страница 20: ...R OPEN 501 STYLE 4 SHORT B L2 248 OFF NETWORK 502 STYLE 4 SHORT A L3 249 INSTALL ERROR 503 STYLE 4 SHORT B L3 250 OR AUDIO TELEPHON 504 STYLE 4 SHORT A L4 251 EXPANDER MODULES 505 STYLE 4 SHORT B L4 252 MANUAL CONTROL 506 STYLE 4 SHORT A L5 253 CAT COMM FAULT 507 STYLE 4 SHORT B L5 254 UNKNOWN 508 Appendix C 3 Error Messages Most error messages are associated with errors in parsing an incoming mes...

Страница 21: ... and you need this new trouble status contact FieldServer 5 Err Unknown OFF NETWORK Node s The FieldServer received a message that a Node either connected or disconnected from the network but no Node number was received it is likely that the message was corrupted Call Tech support 6 Err Unsupported Point Address Format s A message was received from an unsupported device or the address of the devic...