background image

ProtoNode Driver Manual (FS-8700-124) rev 6.doc Manual 

 

 

 

 

 

 

Page 3 of 17 

 
 

ProtoCessor

 1991 Tarob Court Milpitas, California 95035 USA  

Web

:www.protocessor.com 

Tel

: 408.964.4433   

Fax

: 408.964.4425   

Toll_Free

: 800.317.8319   

email

[email protected] 

1.

 

 TIC UPS Description  

The serial TIC UPS driver allows the ProtoNode to transfer data to and from devices over

 

RS-

232 using TIC UPS protocol.  The ProtoNode can emulate a Client.  
This driver is intended for use with Toshiba models UPS.   
It is intended to do the following: 

 

Read information from the UPS such as battery life, voltages etc.  This will be done in 
user mode on the UPS. 

 

Write information and commands such as shutdown commands to the UPS.   

 

Advanced options such as reading/writing EEPROM is not supported.  No date/time 
reads or writes will be supported.  No string type commands will be supported. 

Max Nodes Supported 

ProtoNode Mode 

Nodes 

Comments 

Client 

As the Toshiba protocol only allows for 1:1 communication 
at this stage, only 1 client is allowed per RS-232 port. 

Server 

The server only serves for emulation purposes.  It will have 
a static address as per Toshiba spec. 

 

Содержание FS-8700-124

Страница 1: ...tor Company APPLICABILITY EFFECTIVITY Effective for all systems manufactured after May 1 2001 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 124 TIC UPS Driver Version 1 01 Document Revision 0 ...

Страница 2: ...tion Tips Hints 5 4 CONFIGURING THE FIELDSERVER AS A TIC UPS CLIENT 6 4 1 Data Arrays Descriptors 6 4 2 Client Side Connection Descriptions 7 4 3 Client Side Node Descriptors 7 4 4 Client Side Map Descriptors 8 4 4 1 FieldServer Related Map Descriptor Parameters 8 4 4 2 Driver Related Map Descriptor Parameters 8 4 5 Map Descriptor Example 9 4 5 1 Example 1 9 4 5 2 Example 2 9 APPENDIX A COMMANDS S...

Страница 3: ...ba models UPS It is intended to do the following Read information from the UPS such as battery life voltages etc This will be done in user mode on the UPS Write information and commands such as shutdown commands to the UPS Advanced options such as reading writing EEPROM is not supported No date time reads or writes will be supported No string type commands will be supported Max Nodes Supported Pro...

Страница 4: ... Technologies for this driver FieldServer Technologies PART Description FS 8917 02 RJ45 to DB9F connector adapter FS 8917 03 RJ45 to DB9M connector adapter FS 8700 124 Driver Manual 2 2 Provided by the Supplier of 3rd Party Equipment 2 2 1 Required 3rd Party Hardware Part Description TIC UPS model 1600 1800 4200 G8000 G8000MM G9000 2 2 2 Required 3rd Party Software None 2 2 3 Required 3rd Party Co...

Страница 5: ...LOUR Rx RJ45 01 DB9F 03 WHITE GND RJ45 04 DB9F 05 GREEN Tx RJ45 08 DB9F 02 BLUE BASE NAME FILE NAME FS 8700 124 PROTONODE TOSHIBA UPS CONNECTION DIAGRAM DATE 10 10 07 BY MC 408 262 2299 8917 02 WIRE LIST Toshiba UPS DB9M DB9F FUNCTION FROM TO COLOUR Rx RJ45 01 DB9M 02 GREY GND RJ45 04 DB9M 05 GREEN Tx RJ45 08 DB9M 03 BLUE 8917 03 WIRE LIST PROTONODE 3 1 Hardware Connection Tips Hints The RTS DTS s...

Страница 6: ...routing of data required In order to enable the FieldServer for TIC UPS communications the driver independent FieldServer buffers need to be declared in the Data Arrays section the destination device addresses need to be declared in the Client Side Nodes section and the data required from the servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be fou...

Страница 7: ...ndshaking Specify hardware handshaking None Poll _Delay Time between internal polls 0 32000 seconds 0 05 seconds Example Client Side Connections Connections Port Protocol Baud Parity Handshaking Data_Bits Poll_Delay P1 TOSH_UPS 1200 Even None 7 0 100s 4 3 Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric charac...

Страница 8: ...of this Map Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Data Array section above Data_Array_Offset Starting location in Data Array 0 to maximum specified in Data Array section above Function Function of Client Map Descriptor RDBC WRBC WRBX 4 4 2 Driver Related Map Descriptor Parameters...

Страница 9: ... Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Toshiba_Command Length Scan_Interval B1 DA_DI_01 23 RDBC Node_A ALARM 1 5 B2 DA_DI_01 15 RDBC Node_A ALARM 4 5 B3 DA_DI_01 0 RDBC Node_A ALARM 23 5 For all commands except FAULT and ALARM ensure that the Data_Array_Name points to an array of type float Make sure the Toshiba command supports the selected funct...

Страница 10: ... Tarob Court Milpitas California 95035 USA Web www protocessor com Tel 408 964 4433 Fax 408 964 4425 Toll_Free 800 317 8319 email sales protocessor com Appendix A Commands Specific to Devices Appendix A 1 Client Read commands The following commands are supported with the RDBC function ...

Страница 11: ...tery rated holding time BT Battery temperature BVP Battery voltage percentage DCBV DC bus voltage FAULT Fault data IC1 Input current phase 1 IC2 Input current phase 2 IC3 Input current phase 3 IFRQ Input frequency IV1 Input voltage phase 1 IV2 Input voltage phase 2 IV3 Input voltage phase 3 OC1 Output current phase 1 OC2 Output current phase 2 OC3 Output current phase 3 OFRQ Output frequency OLP1 ...

Страница 12: ...ts Bit Function Bit 23 Not used Bit 22 1 Bit 21 Input over current Bit 20 DC over current Bit 19 DC bus over voltage Bit 18 DC bus under voltage Bit 17 Phase rotation error Bit 16 DC Bus imbalance Bit 15 Not used Bit 14 1 Bit 13 EEPROM error Bit 12 Battery or charger circuit fault Bit 11 Battery overheat Bit 10 UPS overheat Bit 9 0 Bit 8 Fuse has opened Bit 7 Not used Bit 6 1 Bit 5 Inverter over c...

Страница 13: ... 19 Parallel running mode Bit 18 0 Bit 17 0 Bit 16 UPS lifetime alarm Bit 15 Not used Bit 14 1 Bit 13 Asynchronous operation Bit 12 Ambient overheat Bit 11 Overload accumulation started Bit 10 0 Bit 9 0 Bit 8 0 Bit 7 Not used Bit 6 1 Bit 5 Countdown started for shutdown Bit 4 0 Bit 3 0 Bit 2 0 Bit 1 0 Bit 0 0 Appendix A 1 3 STATUS command Stored in bits make sure array s length is 8 and its type i...

Страница 14: ...BLR BPC BPV3 BPC BPV1 BPFREQ BPC BPC BPFREQ BPC BRHT BPFREQ BPFREQ BRHT BPFREQ BVP BRHT BRHT BT BRHT DCBV BVP BVP BVP BT FAULT DCBV DCBV FAULT BVP IC1 FAULT FAULT IC1 DCBV IC2 IC1 IC1 IFRQ FAULT IC3 IC2 IC2 IV1 IC1 IFRQ IC3 IC3 OC1 IFRQ IV1 IFRQ IFRQ OFRQ IV1 IV2 IV1 IV1 OLP1 OC1 IV3 IV2 IV2 OV1 OFRQ OC1 IV3 IV3 SAD OLP1 OC2 OC1 OC1 STATUS OV1 OC3 OC2 OC2 SOB OFRQ OC3 OC3 SAD OLP1 OFRQ OFRQ STATUS...

Страница 15: ...ax 408 964 4425 Toll_Free 800 317 8319 email sales protocessor com Command Description SAD Shutdown after delay BTEST Battery Test2 Appendix A 2 1 Commands supported by different models 1600 1800 4200 G8000 G8000MM G9000 SAD SAD SAD No Write commands supported BTEST BTEST BTEST 2 Please note that due to battery health this point can only be tested as specified by TIC ...

Страница 16: ...nia 95035 USA Web www protocessor com Tel 408 964 4433 Fax 408 964 4425 Toll_Free 800 317 8319 email sales protocessor com Appendix B Troubleshooting Tips Appendix B 1 Connection Tips Hints 1 What should the baud rate in my configuration file be set to Consult the UPS manual for the default baud rate of your UPS ...

Страница 17: ...4 rev 6 doc Manual Page 17 of 17 ProtoCessor 1991 Tarob Court Milpitas California 95035 USA Web www protocessor com Tel 408 964 4433 Fax 408 964 4425 Toll_Free 800 317 8319 email sales protocessor com THIS PAGE INTENTIONALLY LEFT BLANK ...

Отзывы: