Appendix A.1.2.
ALARM command:
Stored in bits, make sure array’s length is 24 and its type is bits.
Bit #
Description
Bit 23:
Not used
Bit 22:
1
Bit 21:
Low battery voltage
Bit 20:
Battery replacement alarm
Bit 19:
Parallel running mode
Bit 18:
0
Bit 17:
0
Bit 16:
UPS lifetime alarm
Bit 15: Not used
Bit 14: 1
Bit 13:
Asynchronous operation
Bit 12:
Ambient overheat
Bit 11:
Overload accumulation started
Bit 10:
0
Bit 9:
0
Bit 8:
0
Bit 7:
Not used
Bit 6:
1
Bit 5:
Countdown started for shutdown
Bit 4:
0
Bit 3:
0
Bit 2:
0
Bit 1:
0
Bit 0:
0
Appendix A.1.3.
STATUS command:
Stored in bits, make sure array’s length is 8 and its type is bits.
Bit #
Description
Bit 7:
Not used
Bit 6:
1
Bit 5:
UPS fault detected
Bit 4:
Input voltage out of spec
Bit 3:
Low battery voltage detected
Bit 2:
UPS output from bypass
Bit 1:
UPS output from inverter
Bit 0:
UPS input and output voltage sync