![FieldServer FS-8700-114 X30 Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/fieldserver/fs-8700-114-x30/fs-8700-114-x30_driver-manual_2287885007.webp)
FS-8700-114 DeviceNet Master Manual
Page 7 of 15
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
4.2.
Client Side Connection Descriptors
Section Title
Connections
Column Title
Function
Legal Values
Adapter
Adapter Name
DNet
Protocol
Protocol name
X30_DNet_Master
DNet_Master_Baudrate
1
Baudrate
125K , 250K , 500K
Command_DA_Name
Commanding Scanner
Status_DA_Name
Provide Scanner status
Name of a data array declared
under Data Arrays section, length of
8 - Bit data array type recommended
Example
// Server Side Connections
Connections
Adapter, Protocol,
DNet_Master_Baudrate, Command_DA_Name, Status_DA_Name
DNet,
X30_DNet_Master, 500K,
Command_Reg,
Status_Reg
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric characters
Node_ID
MAC ID of Slave to scan
0 - 63
Protocol
Specify protocol used
X30_DNet_Master
Example
// Server Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol
DN1,
01,
X30_DNet_Master
1
If System_Station_Address has not been defined in the CSV file, the DIP switch value for both MacID
and Baudrate will be used and the baud parameter in the CSV file will be ignored.