5.3.2
Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch
data from
One of the Node names specified in “Client Node
Descriptor” above
Data_Type
8
Specify memory area
Address_Type = ADU
Coil, Discrete_Input, Input_Register, Holding_Register,
Single_Coil, Single_Register, Slave_Id
Address_Type = PDU
FC01, FC02, FC03, FC04,
FC05, FC06, FC15, FC16
Address_Type = Modicon_5digit
- (Dash), Single_Register, Single_Coil
Address
Starting
address
of
read block
Address_Type = ADU
1-65536
Address_Type = PDU
0-65535
Address_Type = Modicon_5digit
40001, 30001, etc
Length
Length
of
Map
Descriptor.
1-125 (For Analog polls),
1-800 (For Binary polls).
Data_Array_Low_Scale*
Scaling zero in Data
Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
0
Data_Array_High_Scale*
Scaling max in Data
Array
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
100
Node_Low_Scale*
Scaling
zero
in
Connected Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
0
Node_High_Scale*
Scaling
max
in
Connected Node
Any signed 32 bit integer in the range:
-2,147,483,648 to 2,147,483,647.
100
5.3.3
Timing Parameters
Column Title
Function
Legal Values
Scan_Interval* Rate at which data is polled 0-32000,
1
8
Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced