FS-8700-01 Modbus RTU/ASCIIFS-8700-01_Modbus_RTU Driver Manual
Page 22 of 22
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
For Address_Type Modicon_5digit
Address range Data_Type
Function Code (Write)
40001 - 49999 Single_Register 6
30001 - 39999 Single_Coil
5
Appendix E.2.1.
Example:
FC 6 = Write Single Register
Add a parameter to the Modbus client side Map Descriptor called Data_Type.
If you specify the Data_Type as Single_Register and the Function as WRBC or WRBX, then a Modbus poll with FC 6
will be generated.
Logically Single Register implies a length of one, and even if you try to set the length longer in the csv file, the
length is limited to 1 in the driver.
Appendix E.3.
Read/write Operation
When using the driver as a Modbus master, the function RDBC allows read/write capability with Register and Coil
data types. If defaults are used, then Function codes 5 and 6 (Single Writes) are used to write data back to the
registers being read, regardless of data length being read. If multiple writes (FC 15 and 16) are needed for
Read/write operation, the user needs to specify the Node_Type parameter in the Client Side Nodes Section and set
it to Block_Mode.
Note that block writes of length 1 are currently all that is supported.